Fuses; Arc Welding Precautions - Lochinvar EcoForce EF80 Installation, Commissioning, User And Maintenance Instructions

Wall mounted gas fired condensing water heater
Table of Contents

Advertisement

SENSOR
S1
S2
S3
S6
11.2.2
Senor values
Temperature
Resistance
(°C)
(Ω)
-30
175203
-25
129289
-20
96360
-15
72502
-10
55047
-5
42158
0
32555
5
25339
10
19873
15
15699
11.2.3
Conversion table temperature vs resistance for all sensors
F
USES
The E
F
™ has four internal fuses. Three will automatically reset, the fourth is rated at 3.15 A, and is located at the rear of the main
CO
ORCE
control board.
A
W
P
RC
ELDING
RECAUTIONS
The appliance must be isolated from the mains electricity supply in the event of electric arc welding being carried out on any connecting
pipework.
SENSOR TYPE
Internal flow sensor
Internal return sensor
Tank sensor
Flue gas sensor
Temperature
Resistance
(°C)
20
12488
25
10000
30
35
40
45
50
55
60
65
Temperature
(Ω)
(°C)
70
75
8059
80
6535
85
5330
90
4372
95
3605
100
2989
105
2490
110
2084
115
SENSOR VALUE
NTC-10K
NTC-10K
NTC-10K
NTC-10K
Resistance
Temperature
(Ω)
(°C)
1753
120
1481
125
1256
130
1070
135
915
140
786
145
677
150
586
155
508
160
443
165
Resistance
(Ω)
387
339
298
262
232
206
183
163
145
130
48