Fire detection system
Table of Contents

Advertisement

Project planning of indication and operation devices
5

Fire terminal

5.3 Fire terminal

5.4 Fire terminal (Touch) FT2080-A1

5.5 LED indicator (internal) FTO2002-A1

1
2
(1) LED red
(2) LED yellow
(3) Inscribable fields
42 | 242
Building Technologies
Fire Safety
Example of a fire terminal FT2040
The fire terminal is an operating unit built into a housing (Eco) and does not
normally contain a power supply. Supply is ensured by means of an external 24 V
power supply unit. As an option, the fire terminal may be operated with a power
supply unit (70 W) and batteries. For details, see document 008836.
The fire terminal FT2040 is planned in the same manner as a fire control panel.
The fire terminal (Touch) FT2080-A1 is an operating unit that is used remotely
from a ↑ station and which can be installed in a separate housing.
The fire terminal (Touch) has a touch-sensitive 12"-screen and an additional
indication and operating unit in accordance with EN 54-2.
The LED indicator (internal) FTO2002-A1 comprises 24 indicator zones. Each
↑ zone includes a red and a yellow LED.
Any events can be assigned to the LEDs. Each LED may be configured as a
static or flashing indicator. Normally the LED indicator is used as a zone
indicator.
The LED indication (internal) is connected to the station-internal bus and is
cascadable up to a maximum number of five LED indicators (internal).
The LED indicator (internal) is not individually available as an option. It is
permanently integrated in the following components:
Operating unit with LED indicator (internal) FCM2002-A2
(with PMI & mainboard FCM2004)
3
Operating unit with LED indicator (internal) FCM2029-A2
(with PMI & mainboard FCM2027)
Operating add-on with 2 LED indicators (internal) FCM2006-A2
Operating add-on with 4 LED indicators (internal) FCM2007-A2
The operating units and operating add-ons are permanently integrated
depending on the station type. The number of indicator zones required
determines which ↑ station must be ordered.
008843_v_en_--
2015-12-15