Supply Concept - Siemens FS20 Planning Manual

Fire detection system
Table of Contents

Advertisement

Determining the compact stations
11

Supply concept

Use
Electrically isolated control
of various functions [NL]
Connection of remote
transmission devices with
multiple alarm criteria [CH]
Connection with flexible
leads to the options on the
operating unit (instead of
massive conductors)
Connection of shieldings to
earth
↑ Extended networking via
FCnet/LAN or optical
Ethernet
Connection to external
(public) or company
network
11.2 Supply concept
Use
AC 230 V + batteries
AC 230 V
2 x DC 24 V
1 x DC 24 V
146 | 242
Building Technologies
Fire Safety
Required components
RT interface [NL] FCI2005-N1
RT interface [CH] FCI2006-C1
Cable set (communication)
FCA2014-A1
Ethernet switch (modular) FN2012-A1
Firewall
Table 41: Additional components for the stations
The operating current of the sounder module is a maximum of 2 A (fuse
1
protection 2 AT), although the maximum output current per sounder is 1 A.
I
= 2 A = I
+ I
total max.
Out1
If the sounder module FCA2005 is supplied via the FS20 peripheral module (output
VSYS), the availability of a maximum current of 1 A (1 A fuse) on this output must
be observed. The maximum operating current I
See also
2 License keys [➙ 100]
The ↑ stations are fed with energy in different ways. In this chapter the different
types of energy supply are described in detail.
FC20xx
Standard
Possible
No
No
Also observe the notes relating to lightning protection in document A6V10225306.
Notes
Assembled kit with mounting plate,
card E3G091 and connection cable.
Mounted instead of the shield
connection terminal blocks. Can be
used universally for all stations.
2 shield connection terminal blocks,
8 cable clamps on one terminal strip,
and 4 shielded, pre-assembled
cables
Replaces FN2008-A1. Also requires:
+ I
+ I
Out2
Out3
Out4
total max
FT2040
Optional
Optional
Standard
Possible
Connection module (MoNet)
FCA2031-A1
Ethernet module (MM) VN2002-
A1 or Ethernet module (SM)
VN2003-A1
Mounting kit (switch) FHA2029
is only 1 A in this case.
008843_v_en_--
2015-12-15