Operation With Third Power Supply Source [Fr] - Siemens FS20 Planning Manual

Fire detection system
Table of Contents

Advertisement

11.2.5 Operation with third power supply source [FR]

Building Technologies
Fire Safety
The third supply input is used to ensure a reduced degraded mode operation
should the power supply fail (in accordance with EN 54-2, chap. 8.4). The third
supply input can be used in all fire control panels, including the FC2080.
This operation mode ensures emergency power supply for the following functions:
Buzzer
Fault LED indicators
Input voltage on the periphery board and on the fire terminal board:
Nominal DC 9 V
Range DC 7...30 V
A battery holder for 9 V block batteries is available as an option.
Option: FCA2010-F1, battery kit (6LR 61 9 V)
Battery types: 6LR6, 6AM6, 'E-block'
Determining the compact stations
Supply concept
11
149 | 242
008843_v_en_--