7.2

Control terminal limits (CT/CI)

7.2.1
Maximum number of texts
reduce number of
visible AREAS or
use an additional
control terminal
maximum
number of texts
no
< X ?
yes
the required number of
control terminals is defined
Fire & Security Products
Siemens Building Technologies Group
define the required number of
control terminals by going
through this flow chart
The number of texts of other stations (i.e. AREAS) that can be displayed on one control
terminal (CT/CI) is limited.
The following calculation must be used:
twice the number of visible SECTIONS
+ the number of visible ZONES
+ the number of visible ELEMENTS with element text
= number of texts
Limit for 'CT1142' (B3Q460/480/670, B3Q660/680/685)
The max. number of texts is fix 8500.
Limit for 'CI1142' (B3Q460/480/670, B3Q660/680/685)
The max. number of texts is depending on the number of devices already configured in
the control unit.
Number of texts per 100 not configured devices in the control unit
1100
1050
1000
950
900
850
800
750
700
650
600
550
500
450
400
350
Example:
300
Average number of ELEMENTS per ZONE: 5 = 540 texts per 100 devices
250
Free RAM space: 600 devices
200
150
–> maximum number of texts: 540 x 6 = 3240 texts
100
50
0
1
2
3
Ü The given limits for the station (CI/CC), the gateway (CK) and the AlgoWorks utility
programs have to be checked as well!
540
(according to example in graphic chapter 7.1.1)
4
5
6
7
ELEMENTS per ZONE
8
9
10
21
e4595e−7
05.2003