6.5.19.2 Chemical pump
Activate the relay output during the service based upon the volume of treated water.
Note
Only visible in metered systems.
Note
This parameter has two steps. The first one determines the volume which activates the
relay. The second one determines how long the relay has to be activated once the volume
has passed.
AY Activate the relay with
→ Default setting: disabled
AZ Press
to validate the selection and advance to the next
parameter.
BA Set the relay activating time with
BB Press
to validate the selection and advance to the next
parameter.
BC Set the relay deactivating time with
BD Press
to validate the selection and advance to the next
parameter.
Ref. MKT-IM-010 / B - 28.05.2018
Installer Manual Fleck 3150 - NXT - Programming
and
.
,
and
,
and
Relay disabled 10 min. after
the start of regeneration
AUX RELAY OUTPUT
END:
Relay enabled during cycle 2
as in chapter 6.5.18.
AUX RELAY OUTPUT
START:
AUX RELAY OUTPUT
END:
Disabled
CHEMICAL PUMP:
Relay enabled every 20 litres
.
CPO AUX RELAY
VOLUME:
Relay enabled for 1 min.
.
CPO AUX RELAY
TIME:
00:10:00
00:10:00
01:20:00
DISABLED
0020
L
00:01:00
69 / 122