Troubleshooting With The Inverter Led; Troubleshooting With The Basic Operator Panel; Table 6-1 Inverter Led Indication - Siemens MICROMASTER 411 Operating Instructions Manual

Siemens welding system - ac/dc welding inverter user manual
Hide thumbs Also See for MICROMASTER 411:
Table of Contents

Advertisement

6 Troubleshooting
WARNING
Repairs on equipment may only be carried out by Siemens Service, by repair
centers authorized by Siemens or by qualified personnel who are thoroughly
acquainted with all the warnings and operating procedures contained in this
manual.
Any defective parts or components must be replaced using parts contained in
the relevant spare parts list.
Disconnect the power supply before opening the equipment for access.
6.1

Troubleshooting with the Inverter LED

Check the status of the LED located within the control potentiometer.
A list of the LED status indications are given in Table 6-1.
Table 6-1
Condition
200 ms on / 800 ms off
Continuous on
800 ms on / 200 ms off
500 ms on / 500 ms off
OFF
6.2

Troubleshooting with the Basic Operator Panel

Warnings and faults are displayed on the BOP with Axxx and Fxxx respectively.
If the motor fails to start when the ON command has been given:
Check that P0010 = 0.
Check that a valid ON signal is present.
Check that
Check that the setpoint is present (0 to 10 V on Terminal 7) or the setpoint has
been entered into the correct parameter, depending upon the setpoint source
(P1000). For further details see the Parameter List.
If the motor fails to run after changing the parameters, set P0010 = 30 then P0970
= 1 and press P to reset the inverter to the factory default parameter values.
By using a switch between terminals 1 and 4 on the I/O board, the drive should
now run to the defined setpoint (established by analog input and/or control
potentiometer).
NOTICE
For the MICROMASTER 411 the motor data must relate to the inverter data power
range and voltage.
80
Inverter LED Indication
Power On / Ready
Running
Warning (general)
Trip (general)
Off/Mains supply fault / No inverter power
P0700 = 2 (for Terminal I/O control) or
P0700 = 1 (for BOP control).
MICROMASTER 411 & COMBIMASTER 411
Status
Issue 03/01
Operating Instructions
6SE6400-5CA00-0BP0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Combimaster 411

Table of Contents