Issue 03/01
10.9

Harmonic Currents

10.9.1
Harmonic currents with 1% mains impedance
Table 10-8
Three Phase 400 V Connection
MLFB
Filter Type
6SE6411-6UD13-7AA1
unfiltered
6SE6411-6BD13-7AA1
Class B
6SE6411-6UD15-5AA1
unfiltered
6SE6411-6BD15-5AA1
Class B
6SE6411-6UD17-5AA1
unfiltered
6SE6411-6BD17-5AA1
Class B
6SE6411-6UD21-1AA1
unfiltered
6SE6411-6BD21-1AA1
Class B
6SE6411-6UD21-5AA1
unfiltered
6SE6411-6BD21-5AA1
Class B
6SE6411-2UD22-2AA1
unfiltered
6SE6411-6BD22-2AA1
Class B
6SE6411-2UD23-0AA1
unfiltered
6SE6411-6BD23-0AA1
Class B
MICROMASTER 411 & COMBIMASTER 411
6SE6400-5CA00-0BP0
Power CT
Fundamental
(kW)
Amps
0.37
1.50
0.55
2.00
0.75
2.60
1.1
3.71
1.5
4.92
2.2
7.89
3
10.09
Operating Instructions
10 Engineering Information
th
5th
7th
11th
13
Amps
Amps
Amps
Amps
0.67
0.46
1.29
1.10
0.79
0.51
1.69
1.42
0.87
0.51
2.13
1.75
1.05
0.53
2.98
2.35
1.11
0.49
3.80
2.95
4.19
3.11
7.01
6.18
4.68
3.45
8.69
7.69
th
17th
19
Amps
Amps
0.15
0.09
0.14
0.11
0.13
0.15
0.18
0.22
0.26
0.28
1.30
0.60
1.05
0.39
145