Technische Daten; Table 7-1 Micromaster 411 / Combimaster 411, Leistungsdaten - Siemens MICROMASTER 411 Operating Instructions Manual

Siemens welding system - ac/dc welding inverter user manual
Hide thumbs Also See for MICROMASTER 411:
Table of Contents

Advertisement

7 Specifications
7.1

Technische Daten

Table 7-1
MICROMASTER 411 / COMBIMASTER 411, Leistungsdaten
Eigenschaften
Power supply Operating Voltage &
Power Ranges
Input Frequency
Cos phi
Inverter Efficiency
Overload Capability
Inrush Current
Control Method
Pulse Frequency
Fixed Frequencies
Skip Frequencies
Setpoint Resolution
Output Frequency Resolution
Digital Inputs
Analogue Input
Relay Output
Serial Interfaces
Electromagnetic Compatibility
Braking
Protection Level
Operating Temperature
Storage Temperature
Humidity
Operational Altitudes
Protection Features
Standards
CE Marked
Design/Manufacture
94
Werte
380 to 480 V
10% 3AC
47 to 63 Hz
0,95
94 % to 97 % at maximum power
50 % overload capability for 60 s within 5 min referred to the nominal output
current
Less than 4 A for CSB and less than 7.7 A for CSC.
Linear V/f; Flux Current Control (FCC); Quadratic V/f; Multi-point V/f.
2 kHz to 16 kHz (2 kHz steps) 4 kHz default
7, programmable
4, programmable
0.01 Hz Digital, 0.01 Hz Serial, 10 bit Analog
0.01 Hz Digital, 0.01 Hz Serial, 10 bit Analog
3, programmable (isolated), switchable active high / active low (PNP/NPN)
1, for target value or PI input (0 V to 10 V, scalable or can be used a 4th
digital input)
1, programmable 30 V DC / 5 A (resistive), 250 V AC 2 A (inductive)
RS-232
Optional EMC filters to EN55011 Class B. (Radiated Emission: Class A)
DC Braking, Compound Braking and Electro-mechanical Brake control as
option.
IP66 for MICROMASTER 411
IP55 for COMBIMASTER 411
-10 °C to +40 °C (50 °C with derating)
-40 °C to +70 °C
99% RH – non-condensing
Up to 1000 m above sea level without derating
Undervoltage, Overvoltage, Short circuit, Stall Prevention, Motor
2
Overtemperature I
t (Option for PTC), Inverter Overtemperature
CE
Conformity with EC Low Voltage Directive 73/23/EEC
and Electromagnetic Compatibility Directive 89/336/EEC
In accordance with ISO 14001
MICROMASTER 411 & COMBIMASTER 411
0.37 kW to 3.0 kW
Operating Instructions
6SE6400-5CA00-0BP0
Issue 03/01

Advertisement