Page 2
MICROMASTER 411 / COMBIMASTER 411 Documentation Getting Started Guide Provides for Quick Commissioning of the Inverter. Operating Instructions Gives information about features of the MICROMASTER 411 / COMBIMASTER 411, Installation, Commissioning, Control modes, System Parameter structure, Troubleshooting, Specifications and available options of the MICROMASTER 411 / COMBIMASTER 411.
Page 3
MICROMASTER 411 & COMBIMASTER 411 Operating Instructions User Documentation Valid for Release Inverter Type MICROMASTER 411 & COMBIMASTER 411 Issue 03/01 Issue 03/01 Control Version Overview Installation Commissioning Using the COMBIMASTER 411 MICROMASTER 411 System Parameters Troubleshooting Specifications Options Electro-Magnetic...
Page 4
Further information is available on the Internet under: http://www.siemens.de/micromaster Approved Siemens Quality for Software and Training is to DIN ISO 14001, Reg. No. 2160-01 The reproduction, transmission or use of this document, or its contents is not permitted unless authorized in writing.
Page 5
Customers can access technical and general information at: http://www.siemens.de/micromaster Contact address Should any questions or problems arise while reading this manual, please contact the Siemens office concerned using the form provided at the back this manual. MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Operating Instructions...
Page 6
Earth voltage. This connection is normally used to ground the motor. Use for intended purpose only The equipment may be used only for the application stated in the manual and only in conjunction with devices and components recommended and authorized by Siemens. MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
It is not permissible to open the equipment until 5 minutes after the power has been removed. HP ratings are based on the Siemens 1LA motors and are given for guidance only; they do not necessarily comply with UL or NEMA HP ratings.
Page 8
CAUTION Protect the inverter against physical shocks and vibration during transport and storage. Also be sure to protect it against water (rainfall) and excessive temperatures (see Table on page 94). MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
Page 9
The connection of power, motor and control cables to the inverter must be carried out as shown in Figure 2-10 respectively, to prevent inductive and capacitive interference from affecting the correct functioning of the inverter. MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Operating Instructions...
Page 10
60204, 9.2.5.4) Repair WARNING Repairs on equipment may only be carried out by Siemens Service, by repair centers authorized by Siemens or by qualified personnel who are thoroughly acquainted with all the warnings and operating procedures contained in this manual.
Overview This Chapter contains: A summary of the major features of the COMBIMASTER 411 & MICROMASTER 411 range. MICROMASTER 411 / COMBIMASTER 411 ... 16 Design Features ... 17 MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Operating Instructions...
COMBIMASTER 411 provides for a ready to use Inverter/Motor combination unit MICROMASTER 411 offers an Inverter for adaptation to a compatible motor with terminal boxes of size GK030. Inverters are available in ranges 370 W to 3.0 kW 380/480 V AC for three phase units.
External options for PC communications, Basic Operator Panel (BOP), Advanced Operator Panel (AOP), PROFIBUS communications module Option for integrated class B-filter (interference emission class A) Optional housing for installing PROFIBUS module and EM control module MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Operating Instructions...
Control with Proportional-Integral control function (PI) Multi-point V/f characteristic Protection characteristics MICROMASTER 411: Type of protection up to IP66 (comparable to NEMA 4X) COMBIMASTER 411: Type of protection up to IP55 (comparable to NEMA 4) Overvoltage/undervoltage protection Overtemperature protection for the inverter...
Wiring guidelines to minimize the effects of EMI Details concerning electrical installation Installation after a Period of Storage... 21 Ambient operating conditions... 22 Mechanical Installation MICROMASTER 411... 23 Mechanical Installation COMBIMASTER 411... 30 Electrical Installation... 33 MICROMASTER 411 & COMBIMASTER 411...
Page 20
The connection of power and motor cables to the inverter must be carried out as shown in Figure 2-10 to prevent inductive and capacitive interference from affecting the correct functioning of the inverter. MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
Following a prolonged period of storage, you must reform the capacitors in the inverter. The requirements are listed below. Voltage Figure 2-1 Forming MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Storage period less than 1 year: Storage period 1 to 2 years: Storage period 2 to 3 years:...
Do not install the inverter near sources of electromagnetic radiation. Overheating MICROMASTER 411 / COMBIMASTER 411 are cooled by natural convection. Mount the inverter with the heatsink fins above to ensure optimum cooling. Mounting the inverter with the heatsink upside down is not allowed.
2.3.1 Preparation Remove the MICROMASTER 411 installation kit from the packing. Check packing box contents against the advice note supplied. The installation kit should comprise the following items: Inverter cover Terminal Housing Filter Module &...
Installation Procedure NOTE (MICROMASTER 411 ONLY): Prior to installation it may be necessary to fit an Adaptation Plate to a non-Siemens motor. The Adaptation Plate is prepared by the respective motor manufacturer. Normally the Adaptation Plate makes use of the existing motor gasket.
3. After the knockout has been removed it should be safely discarded and the cable glands fitted as shown in Figure 2-6. MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Terminal Housing Figure 2-6 Operating Instructions Installation of Cable Gland...
5. Any auxiliary equipment that might be fitted (e.g. mechanical brake) is in working order. 6. Protection guards are installed around all moving and live parts and any relevant safety notices displayed. MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
1. All dimensions given in millimeters (and inches). 2. MF dimensions use Motor construction type IMB3. Figure 2-8 COMBIMASTER 411 Case Size B Dimensional Detail MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Frame size 90S and 90L have feet with 2 holes each at the non-drive end.
Operation with Residual Current Device If an RCD (also referred to as ELCB or RCCB) is fitted, the MICROMASTER 411 Inverters will operate without nuisance tripping, provided that: A type B RCD is used.
Access to the power and motor terminals The procedure for accessing the power and motor terminals on the COMBIMASTER 411 & MICROMASTER 411 Inverter is illustrated in Figure 2-10. C copper wire only. For tightening torque see Section 7.3. MICROMASTER 411 & COMBIMASTER 411...
Motor wires should be connected in either star or delta configuration in accordance with the motor rating plate. For cable size and rating refer to Section 7.3. MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 C copper wire only. Use a 4-core cable. If crimp terminals are...
NOTE DIN 3 must be configured to read the PTC input [(P0703 = 29) (external trip)] Figure 2-12 PTC Connections PTC Resistor connects between terminals 4 (+24 V) and 3 (DIN 3). MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
Page 39
Screened motor cables should be used when the motor is mounted separately from the inverter. Maximum motor cable length is 5 meters (16.40 feet). WARNING Safety regulations must not be compromised when installing inverters! MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Operating Instructions right angles.
Commissioning This Chapter contains: A schematic diagram of the MICROMASTER 411 / COMBIMASTER 411 An overview of the commissioning options and the display and operator panels An overview of quick commissioing of the MICROMASTER 411 / COMBIMASTER 411 Block Diagram ... 43 General Information...
Page 42
Only qualified personnel may enter settings in the control panels. Particular attention must be paid to safety precautions and warnings at all times. The COMBIMASTER 411 & MICROMASTER 411 is supplied with default parameter settings that cover the following requirements: The motor rating data, voltage, current and frequency are all compatible with the inverter data.
Switching voltage must b DIN4 24 V max – +24 V(100 mA max) ?????? V or 0 V (isolated) Figure 3-1 COMBIMASTER 411 & MICROMASTER 411 Block Diagram MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Motor Potentiometer Serial Interface RS232 Brake...
Advanced Operator Panel (AOP) or the set-up software contained on the Docu-CD is required. The COMBIMASTER 411/MICROMASTER 411 can additionally be integrated into automation systems via the PROFIBUS module (option) or USS interface. When delivered the inverter has a frequency setpoint range of between 0 Hz and 50 Hz.
Using up to 5 jumpers allows ramp times to be set between 1 - 240 s. Also see Table 3-1. Table 3-1 Ramp Time Adjustment Jumpers Time [s] X20 Time [s] X20 MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
Fan/Pump: M~n2 To change V/f curve from Linear to Quadratic curve. 60 Hz operation To change motor default settings from 50 Hz to 60 Hz. MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Reaction(s) of the inverter Power down Inverter uses the ramp times defined by the current...
Parameters influenced by jumper will have jumper default values Parameters influenced by jumper are not changed Parameters influenced by jumper will have “jumper removed“ default values (normally factory default) Parameters influenced by jumper are not changed MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
Page 49
Further Commissioning via P0004 and P0003 An overview of the parameter structure is given in For a detailed description of parameters, see the NOTE We recommend the commissioning according this scheme. MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Section 5.3 Parameter List. Operating Instructions...
411. The BOP is mounted in an Operator Panel Mounting Kit and connected to the COMBIMASTER 411 & MICROMASTER 411 via the serial interface (see Figure 3-9). The BOP can be used to configure several COMBIMASTER 411 & MICROMASTER 411 Inverters.
Decrease value Figure 3-5 Basic Operator Panel Controls MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Effects The LCD displays the settings currently used by the inverter. Pressing the button starts the inverter. This button is disabled by default. To enable this button set P0700 = 1.
In some cases - when changing parameter values - the display on the BOP shows . This means the inverter is busy with tasks of higher priority. Step to the required value Step to the required value MICROMASTER 411 & COMBIMASTER 411 Result on display Result on display Operating Instructions 6SE6400-5CA00-0BP0...
Page 53
The function button may also be used to acknowledge a fault condition 3.3.4.2 Commissioning with the Advanced Operator Panel (AOP) local Siemens sales office for assistance. 3.3.4.3 Quick commissioning (P0010=1) Mechanical and electrical installation of the inverter must be completed before running „Quick Commissioning“.
Page 54
0 s - 650 s Time taken for motor to decelerate from maximum motor frequency down to standstill. P3900 End Quick Commissioning No Quick Commissioning. Perform Quick Commissioning with factory reset of all other Parameters (Recommended). MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
1. The reset process can take up to 3 minutes to complete. 2. Refer to Parameter P0399 for description on saving motor data sets while performing a reset to the factory defaults. MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Operating Instructions...
1.0 seconds while the inverter is stopped. 3. The inverter is programmed at the factory for standard applications on Siemens four-pole standard motors that have the same power rating as the inverters. When using other motors it is necessary to enter the specifications from the motor's rating plate.
Page 57
With the “Pot = Run” jumper fitted, the control potentiometer provides the ON/OFF command source. In order to provide the unit with a Run command the Control Potentiometer must be turned in a clockwise direction. To switch the unit OFF, turn the Control Potentiometer fully anti-clockwise (OFF position). WARNING...
Link Cable, Part Number 6SE6401-1BL00-0AA0 to the Inverter serial comms port. This arrangement is shown in Figure 3-9. Figure 3-9 Connect BOP/AOP with the MICROMASTER 411 Prerequisites P0010 = 0 (in order to initiate the run command correctly). P0700 = 1 (enables the start/stop button on the BOP).
Page 59
Stopping the Motor When the inverter is being operated using the Run/Stop switch (connected to DIN1) setting the switch to OFF will override the potentiometer setting and bring the motor to a controlled stop. 3.4.4 If the Motor does not start up Refer to Chapter 6.
Using the MICROMASTER 411 / COMBIMASTER 411 This Chapter contains: An explanation of the various methods of controlling the inverter A summary of the types of control of the inverter Frequency Setpoint ... 62 Command Sources (P0700)... 63 OFF and Braking Functions ... 63 Control Modes (P1300) ...
Additional external precautions must be taken, or facilities provided, to ensure safe operation, (e.g. independent limit switches, mechanical interlocks, etc.). COMBIMASTER 411/MICROMASTER 411 operate at high voltages. Certain parameter settings may cause the inverter to restart automatically after an input power failure.
If the ON/OFF1 Command is set to more than one Digital input, only the last set Digital Input is active e.g. DIN3 active. OFF1 can be combined with DC braking or Compound braking. MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Terminal 1 (DIN 1): (P0700=2)
Page 64
Compound Braking is possible with both OFF1 and OFF3. For Compound Braking a DC component is added to the AC current. Set the braking current: see P1135 see P0701 to P0704 see P1233 0, DC braking will be active after see P1236 MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
Control Modes (P1300) The various modes of operation of the MICROMASTER 411 control the relation- ship between the speed of the motor and the voltage supplied by the inverter. A summary of the control modes available are listed below: Linear V/f control Can be used for variable and constant torque applications, such as conveyors and positive displacement pumps.
Page 66
4 Using the MICROMASTER 411 / COMBIMASTER 411 Issue 03/01 MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
System Parameters This Chapter contains: An overview of the parameter structure of the MICROMASTER 411 / COMBIMASTER 411 A parameter list in short form Introduction to System Parameters... 68 Parameter Structure ... 69 Parameter List (short form) ... 70 MICROMASTER 411 & COMBIMASTER 411...
Parameters can only be changed by using the Basic Operator Panel (BOP), the Advanced Operator Panel (AOP) or Serial Interface. NOTE Full details of the COMBIMASTER 411 /MICROMASTER 411 Parameters can be found in the separate document “COMBIMASTER 411/MICROMASTER 411 – Parameter List”.
Act. power stack code number P0201 Power stack code number r0203 Act. inverter type r0204 Power stack features r0206 Rated inverter power [kW] / [hp] r0207 Rated inverter current Default Default Default Default MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
Page 71
P0611[1] Motor I2t time constant P0614[1] Motor I2t overload warning level P0640[1] Motor overload factor [%] P1910 Select motor data identification r1912[1] Identified stator resistance MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Default Default 3.25 0.75 0.000 50.00 1.000 1.000 4.00000 100.0...
Page 73
Inhibit reverse direction of MOP P1040[1] Setpoint of the MOP r1050 CO: Act. Output freq. of the MOP P1058[1] JOG frequency right P1059[1] JOG frequency left MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Default 722:2 19:13 19:14 100.0 Default 0.00 5.00 10.00...
Page 74
Holding time after ramp down P1232[1] DC braking current P1233[1] Duration of DC braking Default 10.00 10.00 755:0 755:1 0.00 50.00 0.00 0.00 0.00 0.00 2.00 10.00 10.00 0.00 0.00 0.00 0.00 5.00 Default MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
Page 75
P1340[1] Imax controller prop. gain P1341[1] Imax controller integral time r1343 CO: Imax controller freq. output r1344 CO: Imax controller volt. output P1350[1] Voltage soft start MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Default 10.00 Default 50.0 20.0 0.00 0.00 0.00 10.0...
Page 76
P2051[4] CI: PZD to CB r2053[5] CB identification r2054[7] CB diagnosis r2090 BO: Control word 1 from CB r2091 BO: Control word 2 from CB Default 50.00 1000 0.10 52:0 52:0 52:0 MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
Notes on troubleshooting with the BOP A list of the alarms and fault messages Troubleshooting with the Inverter LED... 80 Troubleshooting with the Basic Operator Panel... 80 Faults and Alarms ... 81 MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Operating Instructions...
By using a switch between terminals 1 and 4 on the I/O board, the drive should now run to the defined setpoint (established by analog input and/or control potentiometer). NOTICE For the MICROMASTER 411 the motor data must relate to the inverter data power range and voltage. Status Power On / Ready...
Required braking power must lie within specified limits NOTE Higher inertia requires longer ramp times; otherwise, apply braking resistor. F0003 UnderVoltage Possible Causes Main supply failed MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 button on the BOP or AOP Operating Instructions OFF2 OFF2...
Page 82
F0015 Motor temperature signal lost Possible Causes Open or short circuit of motor temperature sensor. If signal loss is detected, temperature monitoring switches over to monitoring with the motor thermal model MICROMASTER 411 & COMBIMASTER 411 OFF2 OFF2 OFF1 OFF2...
Page 83
2: Identified stator resistance less than 0.1 % or greater than 100 %. 3: Identified rotor resistance less than 0.1 % or greater than 100 %. 4: Identified stator reactance less than 50 % and greater than 500 % MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Operating Instructions...
Page 84
Internal communications failure Diagnose & Remedy If fault persists, change inverter Contact Service Department F0070 CB setpoint fault Possible Causes Check if motor data in P0304 to P0311 are correct MICROMASTER 411 & COMBIMASTER 411 OFF2 OFF2 OFF2 OFF2 OFF2 OFF2...
Page 85
Diagnose & Remedy Change value of P2268 Adjust feedback gain F0222 PID Feedback above max. value Possible Causes PID feedback above max. value P2267 Diagnose & Remedy MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Operating Instructions OFF2 OFF2 OFF2 OFF2 OFF2...
Ambient temperature could be higher than specified for the inverter A0505 Inverter I Possible Causes Warning level (P0294) exceeded, output frequency and/or pulse frequency will be reduced if parameterized (P0290) Diagnose & Remedy Check the following: MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Operating Instructions...
Page 88
If encoder fitted, check correct encoder selected (check encoder set-up in P0400). Check connections between encoder and inverter Check encoder not faulty (select P1300 = 0, run at fixed speed, check encoder feedback signal in r0061) Increase encoder loss threshold in P0492 MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
Page 89
CB (communication board) specific Diagnose & Remedy See CB user manual A0707 CB warning 8 Possible Causes CB (communication board) specific Diagnose & Remedy See CB user manual A0708 CB warning 9 Possible Causes MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Operating Instructions...
Page 90
Fault value = 0: Parameter settings for output identical 1: Parameter settings for input identical 2: Parameter settings for input do not correspond to ADC type A0921 DAC parameters not set properly Possible Causes MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
Specifications This Chapter contains: The common technical data to the MICROMASTER 411 / COMBIMASTER 411 Inverters The wire sizes and terminal torques Divided into several tables - an overview of the specific technical data of every MICROMASTER 411 / COMBIMASTER 411 Inverter Technische Daten ...
Technische Daten Table 7-1 MICROMASTER 411 / COMBIMASTER 411, Leistungsdaten Eigenschaften Power supply Operating Voltage & Power Ranges Input Frequency Cos phi Inverter Efficiency Overload Capability Inrush Current Control Method Pulse Frequency Fixed Frequencies Skip Frequencies Setpoint Resolution Output Frequency Resolution...
Case Size Rating Information Table 7-2 Case Size B MICROMASTER 411 / COMBIMASTER 411 Frame size: 2 pole 4 pole Motor Output Rating Operating Input Voltage (rms) Operating Input Frequency Output Frequency 2 pole 4 pole Inrush Current Input Current (rms)
Fuses and Circuit Breakers Table 7-6 MICROMASTER 411/COMBIMASTER 411 Fuses and Circuit Breakers Inverter MICRO MICROMASTER 411 COMBIMASTER 411 (without filter) 380 V to 480 V 3 AC MICROMASTER 411 COMBIMASTER 411 (with Class B filter) 380 V to 480 V 3 AC MICROMASTER 411 &...
Options An overview of the options available for the MICROMASTER 411 / COMBIMASTER 411 is given in this section. For further information about options, please refer to the catalog or the documentation CD. MICROMASTER 411/COMBIMASTER 411 User Options Description Basic Operator Panel (BOP)
PC to AOP Connection Kit (6SE6400-0AP00-0AA0) PC to AOP Connection Kit (6SE6400-0PA00-0AA0) MICROMASTER 411 & COMBIMASTER 411 Power Supply Adaptor Operating Instructions 6SE6400-5CA00-0BP0...
EN 61000-3-2 "Limits for harmonic current emissions (equipment input <= 16 A per phase)". All Siemens variable speed drives of the MICROMASTER, MIDIMASTER, MICROMASTER Eco and COMBIMASTER ranges, which are classified as "Professional Equipment" within the terms of the standard, fulfill the requirements of the standard.
Voltage Fluctuations, Dips, Unbalance, Frequency Variations Magnetic Fields Electrostatic Discharge Burst Interference Radio Frequency Electromagnetic Field, amplitude modulated Radio-frequency Electromagnetic Field, pulse modulated MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Standard Level EN 55011 Level A1 EN 61800-3 European Amendment EN61800-3-A13 EN 61000-4-2...
Radio-frequency Electromagnetic Field, pulse modulated NOTICE MICROMASTER 411/COMBIMASTER 411 inverters are intended exclusively for professional applications. Therefore, they do not fall within the scope of the harmonics emissions specification EN 61000-3-2. Class A filtered inverters can be used in this environment under “Restricted Distribution”...
* Denotes any value is allowed. 9.1.7 MICROMASTER 411 – EMC Compliance The MICROMASTER 411 inverters will, when correctly installed and put to their intended use, satisfy the requirements of the EEC Directive 89/336/EEC concerning electromagnetic compatibility. If the guidelines on installation to reduce the effects of electromagnetic interference are followed, the devices are sutiable for installation in machines.
Figure 10-1 illustrates the interaction of parameters associated with current limit. Read Only parameters r0027, r0034, r0037 and r0067 help with fault diagnosis. MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
PTC built in, or if two or three motors are connected to the inverter output and require individual protection. Figure 10-2 PTC Resistor Connections minimum, 1.5 k nominal, and 2 k MICROMASTER 411 & COMBIMASTER 411 and greater. The Operating Instructions 6SE6400-5CA00-0BP0...
Check to ensure you have matched the input supply to the inverter. If the supply voltage is too high, you may damage the inverter even if it trips. MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 t limit to be enabled to protect the motor.
(e.g. P1310 = 100, P1312 = 100), to reduce the possibility of overheating. Voltage Boost increases voltage here t function, so boost may be reduced further if MICROMASTER 411 & COMBIMASTER 411 Frequency t function can be Operating Instructions 6SE6400-5CA00-0BP0...
Page 121
10.2.2.2 Implementation on MICROMASTER 411/COMBIMASTER 411 MICROMASTER 411/COMBIMASTER 411 have a built in PI controller that can be enabled by the user to allow for closed loop control. Once the PI controller is enabled (using P2200), the PI controller internally generates the motor frequency necessary to minimize the error between the PI setpoint and the PI feedback.
Page 122
For the majority of applications, this will be in the form of an analogue sensor. The MICROMASTER 411/COMBIMASTER 411 has one analogue input, terminal connections 6 & 7, and the feedback signal can be connected to this input. The source of the PI feedback signal must then be defined using P2264 = 755 (source of PI feedback = analogue input 1).
Page 123
(via the feedback signal) with the desired system behavior. The desired behavior is defined using a setpoint. The user selects the source of the setpoint with parameter P2253. MICROMASTER 411/COMBIMASTER 411 only have one analogue input and this is most commonly used for the feedback signal, so an internal digital setpoint is usually used.
1 V = 10%. The different responses are achieved by varying the settings of P2280 and P2285. Figure 10-4 Quick response with overshoot: P2280 = 0.30; P2285 = 0.03 s Figure 10-5 Quick response with overshoot, but instability:P2280 = 0.55; P2285 = 0.03 s MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
P term (P2280) greater than 0.50. A block diagram showing the relationships and interaction between PI Setpoint and PI Feedback is shown in Figure 10-10 on page 128. MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Operating Instructions...
To allow this, the following parameters are set: P2200 = 0 P1120 = 0,0 s P1121 = 0,0 s P1080 = 50.0 Hz. Figure 10-7 Response to 5 Hz step: L = 100 ms MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
I time = 3L = 0.30 s = P2285 The PI controller should now be enabled (P2200 = 1). Figure 10-9 Step Response in PI control with P2280 = 9.84 and P2285 = 0.30 MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Operating Instructions...
(P0003 = 3). These features are described in the Parameter List. P2254 P2253 BOP link P2253 COM link P2200 COM link ADC2 Figure 10-10 PI Basic Block Diagram to be reached. MICROMASTER 411 & COMBIMASTER 411 (P1080) and Motor control Output Operating Instructions 6SE6400-5CA00-0BP0...
Page 129
Energy Saving Mode, it is necessary to activate the Auto-restart function of the inverter (using P1210=6). NOTES Energy Saving Mode only operates in a positive direction. Energy Saving Setpoint must be greater than f MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Operating Instructions...
P2391 is started. When the energy saving timer has expired, the inverter is ramped down to stop and enters energy saving mode (see diagram below). Figure 10-11 Energy Saving Mode 1 MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
(regeneration) to return to the DC link. To overcome this possibility the MICROMASTER 411/COMBIMASTER 411 employs a number of methods to control braking. These options are described in the following paragraphs.
10.3.2 Vdc Max Controller The MICROMASTER 411/COMBIMASTER 411 has a controller to limit the DC voltage (Vdc Max controller). When braking a load faster than would normally be possible, excess energy has to be dissipated. This energy is unable to go back into the input supply so the result is that the DC link voltage rises.
When using Compound braking, the ramp-down time is defined and the level of current to be used in Compound Braking is defined using P1236. Figure 10-15 Compound Braking MICROMASTER 411 & COMBIMASTER 411 Operating Instructions 6SE6400-5CA00-0BP0...
Permissible rated input voltage as a percentage of the nominal voltage 1000 2000 Installation altitude in meters above sea level Figure 10-17 Derating with Altitude MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 10 20 Permissible rated output current as a percentage of the nominal current 3000...
10.4.3 Derating with Switching Frequency The default switching frequency of the MICROMASTER 411/COMBIMASTER 411 is 4 kHz. This is usually adequate for most applications and will allow full performance to be obtained from all products over the full temperature range.
The MICROMASTER 411 cannot be used on unearthed input supplies. 10.7 Lifetime of Inverters When the inverters are used in conjunction with Siemens motors (1LA7 and 1LA9) the liftetime of the inverter is >= 20,000 hours. MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 t trip will occur (F0005).
(digital, analogue, serial etc.) and outputs (inverter current, frequency, analogue output, relays etc.). The MICROMASTER 411/COMBIMASTER 411 uses a simplified version of BiCo, (which is still very flexible) contained within the parameter set. The system can be set up without using additional software or hardware.
Page 139
Now the inverter will ramp between set points using the normal ramp time as set in P1120 and 1121. However, at switch off from digital input 1, the inverter will turn off with an OFF3, using the ramp rate set in P1135, which may be different to P1121.
Page 140
10.8.3 Using Control and Status Words with BiCo Many MICROMASTER 411/COMBIMASTER 411 read only parameters consist of control words. The parameter is made up of a 16-bit number, each bit representing a particular value. For example, parameter P0052 (Status Word 1) gives various value settings such as Inverter ready (bit 0), or Motor Current Limit (bit b).
6SE6411-6BD21-1AA1 Class B 6SE6411-6UD21-5AA1 unfiltered 6SE6411-6BD21-5AA1 Class B 6SE6411-2UD22-2AA1 unfiltered 6SE6411-6BD22-2AA1 Class B 6SE6411-2UD23-0AA1 unfiltered 6SE6411-6BD23-0AA1 Class B MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Power CT Fundamental (kW) Amps Amps Amps 0.37 1.50 1.29 0.55 2.00 1.69 0.75 2.60 2.13...
The mains short-circuit power may be obtained from the power supply company, or may be read from the Type Plate of the supplying power transformer. 10.11 Power Losses Figure 10-18 shows the power loss for the MICROMASTER 411/COMBIMASTER 411 Inverters. Figure 10-18 Power Losses MICROMASTER 411 / COMBIMASTER 411 Output Frequency MICROMASTER 411 &...
Class 2M2: Class 2M1: The inverter meets class 2M2 for Vibration stress and 2M1 for shock stress in product packaging. MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 EN 60721-3-3 class 3M6 and 3M8 EN60068-2-6, test Fc Class 3M6: 10-58 Hz/ 0.15 mm, 58-200 Hz/ 2g Class 3M6: 10-58 Hz/ 0.15 mm, 58-200 Hz/ 2g...
There are three versions of PROFIBUS: FMS, DP and PA and all these versions will work together. The most commonly used version is the DP version, intended for general industrial applications. This is the version supported by Siemens Drives. 10.13.2 Using the PROFIBUS In order to connect to a PROFIBUS system, a PROFIBUS module is required.
10.14 PROFIBUS Module This option allows the MICROMASTER 411/COMBIMASTER 411 to be controlled via a PROFIBUS-DP serial bus (SINEC L2-DP). PROFIBUS-DP is a cost-effective high-speed serial communication system optimized for the actuator/sensor area where very short system reaction times are critical.
For reliable operation of the serial bus system, the cable must be terminated at both ends using terminating resistors. Bus terminations with the MICROMASTER 411 PROFIBUS Module is achieved using the Bus Termination Switch (see above). Additionally, for 12 MBd operation, no stub length from the main bus cable is allowed.
Dimensions H x W x D Degree of protection Maximum bus speed Table 10-11 PROFIBUS Ordering information Designation PROFIBUS module MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Description 107,8 mm x 128 mm x 40,5 mm IP66 12 MBaud Order No.
10.15 Variant Independent Options Several options are available for use with Siemens Standard inverters. These are intended to assist product selection, installation and commissioning in certain applications. 10.15.1 Basic Operating Panel (BOP) MICROMASTER default settings can be changed through the Basic Operator Panel (BOP) drive option.
Page 153
BOP/AOP Door Mounting Kit for Single Inverter Control This kit is used to mount an operator panel in a cabinet door. It must be used in conjunction with a MICROMASTER 411 5 m cable assembly. The connecting line must be supplied by the user.
Siemens plc operates a quality and environmental management system, which complies with the requirements of ISO 14001. ISO 9001 Siemens plc operates a quality management system, which complies with the requirements of ISO 9001. MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 commutated inverters Safety of machinery –...
Page 159
Installation of Cable Glands · 27 Installation Procedure · 24 Internal Overtemperature · 119 Internet Home Address · 5 Line and Motor Connections · 34 MICROMASTER 411 & COMBIMASTER 411 6SE6400-5CA00-0BP0 Line Connections · 34 Linear V/f control · 65 Main characteristics · 17 Mechanical Installation ·...