Behaviour of the Ramp Time Jumpers
In Table 3-2 the behaviour of the Ramp Time Jumpers are explained:
Table 3-2
Ramp Time Jumper Behaviour
Status before action(s)
No jumper fitted
Ramp times have arbitrary setting
At least one Jumper fitted
Ramp times have arbitrary setting
At least one Jumper fitted
Ramp times have arbitrary setting
NOTE
The brake time is influenced by the setting for the ramp time (deceleration time).
The following relationship applies:
Braking time = P1121 (deceleration time) *
3.3.2
Control Circuit Jumpers
Control Jumpers (see Table 3-3) are provided for the following functions (fit jumper
to enable function). Jumpers can only be accessed when the cover is removed:
Pot = Run
Enables the control potentiometer as the Command Source (auto restart is
enabled).
24 V AIN
To change analogue input range from 0 –10 V to 0 – 24 V
DC Brake
To change Stop function from OFF1 to DC Brake.
Fan/Pump: M~n2
To change V/f curve from Linear to Quadratic curve.
60 Hz operation
To change motor default settings from 50 Hz to 60 Hz.
MICROMASTER 411 & COMBIMASTER 411
6SE6400-5CA00-0BP0
Action(s)
Reaction(s) of the inverter
Power down
Inverter uses the ramp times defined by the current
Fit jumper(s)
jumper setting
Power up
Power down
Inverter uses the ramp times defined by the current
jumper setting
Power up
Power down
Inverter uses the ramp times that were used before
Remove jumper(s)
removing the jumper(s)
Power up
Operating Instructions
3 Commissioning
P0305 (nominal motor current)
r0207 (nominal inverter current)
47