Siemens MICROMASTER 411 Operating Instructions Manual page 39

Siemens welding system - ac/dc welding inverter user manual
Hide thumbs Also See for MICROMASTER 411:
Table of Contents

Advertisement

Issue 03/01
2.5.5
Avoiding Electro-Magnetic Interference
The inverters are designed to operate in an industrial environment where a high
level of EMI can be expected. Usually, good installation practices will ensure safe
and trouble-free operation. If you encounter problems, follow the guidelines stated
below.
Action to Take
Make sure that any control equipment connected to the inverter (such as a
PLC) is connected to the same ground or star point as the inverter via a short,
thick link.
Flat conductors are preferred as they have lower impedance at higher
frequencies.
Separate the control cables from the power connections as much as
possible, using separate trunking, if necessary at 90
Ensure that contactors are suppressed, either with R-C suppressors for AC
contactors, or 'flywheel' diodes for DC contactors, fitted to the coils. Varistor
suppressors are also effective. This is important when the contactors are
controlled from the inverter relay.
Screened motor cables should be used when the motor is mounted separately
from the inverter.
Maximum motor cable length is 5 meters (16.40 feet).
WARNING
Safety regulations must not be compromised when installing inverters!
MICROMASTER 411 & COMBIMASTER 411
6SE6400-5CA00-0BP0
Operating Instructions
2 Installation
0
right angles.
39