Issue 10/06
6.5
Series commissioning
An existing parameter set can be transferred to a MICROMASTER 440 frequency
inverter using STARTER or DriveMonitor (refer to Section 4.1 "Establishing
communications MICROMASTER 440 ⇔ STARTER").
Typical applications for series commissioning include:
1. If several drives are to be commissioned that have the same configuration and
same functions. A quick / application commissioning (first commissioning) must
be carried-out for the first drive. Its parameter values are then transferred to the
other drives.
2. When replacing MICROMASTER 440 frequency inverters.
6.6
Parameter reset of factory setting
START
User access level
P0003 = 1
1
Standard
P0004 = 0
Parameter filter
0
All parameters
Commissioning parameter
P0010 = 30
30
Factory setting
Factory reset
P0970 = 1
0
disabled
1
Parameter reset
The drive inverter carries-out a parameter reset (duration, approx. 10 s) and then
automatically exits the reset menu and sets:
P0970 = 0 :
P0010 = 0 :
END
MICROMASTER 440
Operating Instructions (Compact)
disabled
ready
6 Commissioning
1
0
0
0