6 Commissioning
6.4.6

Analog input (ADC)

ADC type
P0756 = ...
Defines the analog input type and activates the monitoring
function of the analog input.
0
Unipolar voltage input (0 to +10 V)
1
Unipolar voltage input with monitoring
(0 to 10 V)
2
Unipolar current input (0 to 20 mA)
3
Unipolar current input with monitoring
(0 to 20 mA)
4
Bipolar voltage input (-10 to +10 V)
NOTE
For P0756 to P0760, the following applies:
Index 0 : Analog input 1 (ADC1), terminals 3, 4
Index 1 : Analog input 2 (ADC2), terminals 10, 11
P0757 =...
Value x1 of ADC scaling
Value y1 of ADC scaling
P0758 =...
This parameter represents the
value of x1 as a % of P2000
(reference frequency).
P0759 =...
Value x2 of ADC scaling
Value y2 of ADC scaling
P0760 =...
This parameter represents the
value of x2 as a % of P2000
(reference frequency).
P0761 =...
Width of ADC deadband
Defines width of deadband on
analog input.
Delay, ADC signal loss
P0762 = ...
Defines the delay time between the loss of the analog setpoint and fault message F0080
being displayed.
ADC channel
DIP switch
KL3
ADC+
KL4
ADC−
38
0 V
0.0 %
10 V
100.0 %
0 V
P0756
A
ADC
ADC
type
type
D
1.7 V
1
0
3.9 V
ADC1
OFF = [V], 0 - 10 V
ON = [A], 0 - 20 mA
ADC2
OFF = [V], 0 - 10 V
ON = [A], 0 - 20 mA
P0761 > 0
||
0 < P0758 < P0760
0 > P0758 > P0760
%
100 %
4000 h
ASPmax
P0760
P0758
P0757
P0761
P0757 = P0761
ASPmin
P0761
P0753
ADC
dead
scaling
P0756
P0761
Wire
breakage
sensing
P0707
Issue 10/06
x
10 V
100%
P0759
20 mA
10 ms
r0754
P1000
Setpoint
ADC
r0755
Pxxxx
zone
r0752
P0762
T
0
F0080
r0751
r0722
r0722.6
Pxxxx
Function
MICROMASTER 440
Operating Instructions (Compact)
0
7
V
mA