Example:
1. Commissioning steps with a motor:
− Carry-out commissioning at DDS1.
− Connect P0820 (P0821 if required) to the DDS changeover source
− Copy DDS1 to DDS2 (P0819[0] = 0, P0819[1] = 1, P0819[2] = 2).
− Adapt DDS2 parameters
DIN
ADC
DIN4
Commissioning steps with 2 motors (motor 1, motor 2):
2.
− Commission motor 1; adapt the remaining DDS1 parameters.
− Connect P0820 (P0821 if required) to the DDS changeover source
− Changeover to DDS2 (check using r0051).
− Commission motor 2; adapt the remaining DDS2 parameters.
MICROMASTER 440
Operating Instructions (Compact)
(e.g. using DIN 4: P0704[0] = 99, P0820 = 722.3).
(e.g. ramp-up / ramp-down times P1120[1] and P1121[1]).
SUM
AFM
setpoint
P0820 = 722.3
(e.g. via DIN 4: P0704[0] = 99, P0820 = 722.3).
MM4
Sequence control
RFG
0
1
P1120
P1121
[0]
[1]
DDS1
DDS2
DDS3
Motor 1
M1
Motor 2
M2
6 Commissioning
Motor
control
[2]
M
71