Issue 10/06
Starting boost (entered in %)
P1312 =...
Voltage boost when starting (after an ON command) when using the linear or square-law
V/f characteristic as a % relative to P0305 (rated motor current) or P0350 (stator
resistance). The voltage boost remains active until
1) the setpoint is reached for the first time and
2) the setpoint is reduced to a value that is less than the instantaneous ramp-function
generator output.
P1320 =...
Programmable V/f freq.
coord. 1
Sets V/f coordinates
(P1320/1321 to P1324/1325) to
define V/f characteristic.
P1321 =...
Programmable. V/f volt.
coord. 1
Programmable V/f freq.
P1322 =...
coord. 2
Programmable V/f volt.
P1323 =...
coord. 2
Programmable U/f Freq.
P1324 =...
coord. 3
P1325 =...
Programmable V/f volt.
coord. 3
Starting frequency for FCC
P1333 = ...
(entered as a %)
Defines the FCC starting frequency as a
function of the rated motor frequency (P0310).
P0310
=
f
FCC
100
=
f
+
FCC
Hys
NOTE
The constant voltage boost P1310 is
continually decreased analog to switching-in
FCC.
Slip compensation
P1335 = ...
(entered in %)
Dynamically adjusts output frequency of
inverter so that motor speed is kept constant
independent of motor load.
P1338 =...
Resonance damping gain V/f
Defines resonance damping gain for V/f.
MICROMASTER 440
Operating Instructions (Compact)
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
P
1333
P0310
(
)
+
P
1333
6
%
100
V
V
= f(V
, M
V
max
dc
max
max
r0071
V
n
P0304
P1325
P1323
P1321
P1310
f0
f1
f2
0 Hz
P1320
P1322
P1310[%]
r0395[%]
P1310[V]
=
100[%]
100[%]
10.0 %
FCC
V/f
0.0 %
Range of slip compensation :
%
P1335
6 Commissioning
0.0 %
)
f3
f
f
f
n
max
P1324
P0310
P1082
P0304[V
]
f
f
FCC
FCC+Hys
f
out
f
6 % 10 %
100 %
0.00
f
N
49