10
en | Diagrams
2.2.2
D7212GV3 Power Supply Side Wiring Diagram
Callout
Description
1
If required by local AHJ, connect D113
Battery Lead Supervision Module.
2
Batteries
3
D122 Dual Battery Harness, as required
4
D1640 Transformer and D8004 Transformer
Enclosure required for NFPA Applications
5
D8132 Dual Battery Charger with two
batteries (Batteries are not supervised.)
6
Power limited, supervised
7
Power limited
NOTICE!
All external connections except Terminal 5 (battery positive) are power limited.
F.01U.167.105 | 02 | 2010.11
Callout
Description
8
D192G Bell Supervision Module
9
To Relay A or Relay B
10
Listed Audible Signaling Devices rated at 12.0
VDC nominal (Do not use vibrating type horns.)
11
C900V2 (optional)
560 Ω, 2 W EOL Resistor (P/N: 15-03130-005)
12
13
RJ31X, primary telephone line
14
To earth ground
UL Installation Instructions
Control Panels
Bosch Security Systems, Inc.