Power Outputs - Circuit Protection

Three self-resetting circuit breakers protect the control panel from short circuits on the
continuous and programmable power outputs. If the control panel is programmed for power
supervision and a short circuit occurs on one of the power outputs, the control panel sends a
BATTERY LOW or BATTERY MISSING for Bosch Security Systems Modem IIIa
Format, or a Battery Missing/Dead (311) or Low System Battery (302) for Contact ID Format.
One self-resetting circuit breaker protects:
NOTICE!
A short circuit on one terminal disrupts power to the other terminal.
Another self-resetting circuit breaker protects:
NOTICE!
A short circuit on one of the terminals disrupts power to the other two terminals.
The third self-resetting circuit breaker protects Terminal 32: Power +.
NOTICE!
UL requires any device powered from a power output to be supervised.
NOTICE!
UL requires that power outputs are not shared between fire and non-fire devices unless all
devices are in conduit within 20 ft and are in the same room.
3.4

Power Outputs - Total Available Power

The system produces up to 1.4 A of combined power at 12.0 VDC Nominal for all powered
devices. The outputs listed below share the available power. These outputs are shown as red
circles on the faceplate.
Bosch Security Systems, Inc.
Terminal 3: Auxiliary Power
Terminal 24: Zonex Power.
Terminal 6: Alarm Power Output
Terminal 7: Alternate Alarm Power Output
Terminal 8: Switched Auxiliary Power.
Terminal 3 - Auxiliary Power. Use this terminal to power devices requiring continuous
power.
Terminal 6 (Relay A) - Alarm Power Output. Programmable relay normally open, power
on alarm.
Terminal 7 (Relay B) - Alternate Alarm Power Output. Programmable relay normally
open, power on alarm.
Terminal 8 (Relay C) - Switched Auxiliary Power. Programmable relay normally closed,
switches power off when the Sensor Reset command is executed.
Terminal 24 - Zonex Power. Use this terminal to power Zonex modules such as the
D8125, D8128D, and D8129 Modules.
UL Installation Instructions
Power Supply and Power Outputs | en
2
Communication
F.01U.167.105 | 02 | 2010.11
19