Terminal Wiring Requirements - Bosch D9412GV3 Installation Instructions Manual

Hide thumbs Also See for D9412GV3:
Table of Contents

Advertisement

Control Panels
Battery
Discharge
Discharge/
Cycle
Recharge
Schedule
Recharge
Cycle
Environmental
Temperature:
Relative
Humidity:
Arming
D720/D720B Keypads, D1255/D1255B/D1255RB Keypads, D1256/D1256RB Fire Command
Stations
Centers; D1257/D1257RB Fire Alarm Annunciators; D1260/D1260B Keypads; Keyswitch
Point
On-board
Thresholds
Points 1 to 8
Compatible
D8103 Universal Enclosure, D8109 Fire Enclosure, D8108A Attack Resistant Enclosure, BATB-40
Enclosures
Battery Box
4.1

Terminal Wiring Requirements

Terminal
Terminal
No
Description
1
AC
2
AC
3
+ AUX POWER
4
BATTERY -
5
BATTERY +
6
RELAY A
7
RELAY B
8
RELAY C
9
COMMON
10
EARTH
GROUND
11
POINT 1
12
POINT 1/2
COMMON
13
POINT 2
14
POINT 3
Bosch Security Systems, Inc.
13.9 VDC
Charging float level.
13.8 VDC
Charging status LED on.
12.1 VDC
Low Battery and AC Fail Reports if programmed. Low Battery LED
on.
10.2 VDC
Minimum operational voltage.
10.0 VDC
Battery load shed (processing functions continue if AC is
present).
AC ON
Load shed relay resets, battery charging begins, Battery Trouble
and AC Restoral Reports sent.
13.7 VDC
Battery Restoral Report sent, Low Battery LED off.
13.9 VDC
Charging status LED off, battery float charged.
0°C to +50°C (+32°F to +122°F)
Maximum 93% non-condensing
Open
Greater than 3.7 VDC, but less than 5.0 VDC. Greater than 2.0
Normal
VDC, but less than 3.0 VDC. Greater than 0.0 VDC, but less than
Short
1.3 VDC.
Requirements
18 AWG min (up to 14 AWG max)
18 AWG min (up to 14 AWG max)
Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current
Bosch supplied wire lead, included with panel
Bosch supplied wire lead, included with panel
Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current
Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current
Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current
Terminal accommodates 14 to 22 AWG, use appropriate wire size based on current
14 to 16 AWG
Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop
resistance less than 100 Ω
Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop
resistance less than 100 Ω
Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop
resistance less than 100 Ω
Terminal accommodates 14 to 22 AWG, use appropriate wire size based on loop
resistance less than 100 Ω
UL Installation Instructions
Specifications | en
23
F.01U.167.105 | 02 | 2010.11