Setting The Buzzer Volume - Siemens FT2080 Operation Manual

Fire terminal (touch)
Hide thumbs Also See for FT2080:
Table of Contents

Advertisement

5
Operation
Settings / Administration
5.9.5
152
Building Technologies
Fire Safety
4. Select a setting.
a The command execution display confirms successful execution of the
command by displaying
a The touch screen brightness has been set.

Setting the buzzer volume

You can set the sound level of the ↑ 'Station' buzzer on four levels or switch it off.
NOTICE
Buzzer volume too low
Non-compliance with EN 54-2 Para 12.10.2
Set the buzzer sound level to the maximum.
As per EN 54-2, the minimum sound level at a distance of 1 m must reach the
following values, measured under open air conditions:
-60 dB (A) for announcing fire alarm signals
-50 dB (A) for announcing fault messages
'Set buzzer volume'
w You are logged onto 'Access level' 2.2.
w You are in 'Main menu'.
1. Select the 'Settings/administration' menu item.
a The 'Settings/administration' menu is displayed.
.
A6V10380629_en--_a
2015-09-10