Siemens FT2080 Operation Manual page 112

Fire terminal (touch)
Hide thumbs Also See for FT2080:
Table of Contents

Advertisement

5
Operation
Switching off / Switching on
112
Building Technologies
Fire Safety
Switch on detector zone via LT: Option 2
w You are logged onto at least 'Access level' 2.1.
w The 'Zone' is switched off.
1. Follow steps 1 and 2 for option 1.
2. Press <'Options'> in the event command list (ECL).
a The 'Select option' dialog window opens.
3. Select the 'Execute commands' menu item.
a The 'Select command' dialog window is displayed.
4. Select the 'ON' command.
a The 'Zone' is deleted from the event list 'Isolations'.
a The command execution display confirms successful execution of the
command by displaying
a The 'Zone' is switched on.
Switch on detector zone via 'Message summary' dialog window
w You are logged onto at least 'Access level' 2.1.
w The 'Zone' is switched off.
w You are in 'Main menu'.
1. Select the 'Message summary' menu item.
a The 'Message summary' dialog window is displayed.
2. Select the 'Isolations' list display.
a The 'Isolations' event list opens.
3. Follow the instructions for 'Switch on detector zone via LT: Variant 1' from step
2 onwards.
.
A6V10380629_en--_a
2015-09-10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents