Procedure In Case Of Fault - Siemens FT2080 Operation Manual

Fire terminal (touch)
Hide thumbs Also See for FT2080:
Table of Contents

Advertisement

5.2 Procedure in case of Fault

1
Status information
2
Indication of fault location
3
<Silence buzzer>
Building Technologies
Fire Safety
Procedure in the event of a malfunction
Step
Action
1
Press <Silence buzzer> on the ↑ Person Machine Interface
2
Read message/fault location on the display
3
Go to the fault location
4
Eliminate the cause of the fault
A list of possible 'Faults' and how they are eliminated can be found in the chapter
'Faults / Troubleshooting'. If you cannot eliminate 'Fault', please contact your
service provider.
'Fault' and 'Intervention Concept' (IC)
On consideration of 'Intervention Concept', events of the 'Fault' category can be
assigned their own sequence. This sequence may be configured differently and
depends on the ↑ 'Manned operation' / ↑ 'Unmanned operation' operation mode.
An exemplary process following 'Fault', taking in account 'Intervention Concept', is
graphically shown in the 'Intervention Concept (IC) chapter and is outlined below:
'Fault' has occurred
The remote transmission for 'Faults' is activated in 'Unmanned operation'
l
operation mode.
The remote transmission for 'Faults' is activated in 'Manned operation'
l
operation mode unless 'Fault' is acknowledged within the delay t1.
Procedure in case of Fault
4
<Acknowledge>
5
<Reset>
Operation
5
107
A6V10380629_en--_a
2015-09-10