7.4 Building dimensions and ceiling height requirements

The required ceiling height depends on several parameters. The rail system itself - if single-rail or traverse system
is required. The installation location - ceiling or wall, and the required lifting height from floor to hoist.
A traverse system requires a greater ceiling height than a mono-rail system. Wall-mounted rails require greater
ceiling height, since a higher/stronger rail profile must be used.
For wall installation in large rooms, a higher/stronger rail profile is required. Similarly, the traverse rails in large
rooms must be higher/stronger.

7.5 Building dimensions for different track installations

The building dimensions of an installation is defined as the distance between the ceiling underside
and the hooks of the hoist.

7.5.1 Mono-rail

For the EC-Track system and Robin ceiling hoist, the dimensions for being inbuilt, measured from the ceiling with
the rail mounted as close as possible to the ceiling, are:
Ceiling mounted rail profile S
Wall/floor mounted rail profile M
Wall/floor mounted rail profile L
Measured from beneath the rail to the sling hook
40
K
H = 410 mm
H = 450 mm
H = 519 mm
K = 336 mm