Maintenance Bypass Procedure; Switch From Ups To Maintenance Bypass; Switch From Maintenance Bypass To Ups - Toshiba 4200 FA CT User Manual

Three-phase 15/25/30/50 kva ups
Table of Contents

Advertisement

6.16

Maintenance Bypass Procedure

To safely set the unit in Maintenance Bypass, the UPS is first electrically switched to
bypass mode, and then mechanically switched to bypass mode. This prevents the UPS
from being placed in parallel with commercial power.
Follow the instructions below when switching the UPS to and from Maintenance Bypass
Mode.
WARNING

6.16.1 Switch from UPS to Maintenance Bypass

1) Turn the "STOP/RUN" key switch, located on the front panel, to "STOP." Operation
of the UPS inverter stops and the BYP LED illuminates. Output power is now
provided to the load through the Bypass circuit. While in this mode, if a power
failure occurs on the commercial power source, the UPS will lose power.
Power to the critical load device will be interrupted. The battery charging
circuit and chopper circuit remains active.
2) Verify that step one above is followed, and that the BYP LED indicator on the front
panel is illuminated.
3) Locate the maintenance bypass rotary cam switch (middle of inner front panel of
the UPS); slowly rotate the cam switch clockwise to the "BYPASS MODE" position.
4) Turn off MCCB breaker labeled "MAIN POWER SWITCH."
The unit is now in the Maintenance Bypass mode and may be serviced. For units
with internal transformers, the transformers are still energized.
6.16.2

Switch from Maintenance Bypass to UPS

1) Verify that the "STOP/RUN" switch is in the "STOP" position. Turn on MCCB
"MAIN POWER SWITCH."
2) Wait until the output fans turn on (this indicates that the unit is in the Bypass
mode), and that the BYP LED light on the front panel is lit.
3) For units with an external battery cabinet, turn on MCCB "BATTERY CABINET."
4) Locate the maintenance bypass switch (middle of inner front panel of the UPS).
Slowly rotate the cam switch counter-clockwise to the "UPS MODE" position.
5) Turn the "STOP/RUN" switch to the "RUN" position.
6) Verify that the Inverter indicator light on the front panel is lit.
The unit is now back On-Line and supplying conditioned power to the load.
44
TOSHIBA
Failure to adhere to the following instructions could result in damage to your
equipment and/or you risk removal of power to any equipment attached to
the UPS.