Settings - Siemens Siprotec 7VK61 Manual

Breaker management device
Hide thumbs Also See for Siprotec 7VK61:
Table of Contents

Advertisement

Figure 2-20
2.4.3

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
Addr.
Parameter
3501
FCT Synchronism
3502
Dead Volt. Thr.
3503
Live Volt. Thr.
3504
Umax
3507
T-SYN. DURATION
3508
T SYNC-STAB
3509
SyncCB
3510
Op.mode with AR
3511
AR maxVolt.Diff
3512
AR maxFreq.Diff
3513
AR maxAngleDiff
3515A
AR SYNC-CHECK
3516
AR Usy1<Usy2>
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
Example of a single-phase phase-to-earth connection
Setting Options
ON
OFF
ON:w/o CloseCmd
1 .. 100 V
20 .. 125 V
20 .. 140 V
0.01 .. 600.00 sec; ∞
0.00 .. 30.00 sec
(Setting options depend
on configuration)
with T-CB close
w/o T-CB close
1.0 .. 60.0 V
0.03 .. 2.00 Hz
2 .. 80 °
YES
NO
YES
NO
2.4 Synchronism and voltage check (optional)
Default Setting
ON
Synchronism and Voltage Check
function
5 V
Voltage threshold dead line / bus
90 V
Voltage threshold live line / bus
110 V
Maximum permissible voltage
1.00 sec
Maximum duration of synchro-
nism-check
0.00 sec
Synchronous condition stability
timer
None
Synchronizable circuit breaker
w/o T-CB close
Operating mode with AR
2.0 V
Maximum voltage difference
0.10 Hz
Maximum frequency difference
10 °
Maximum angle difference
YES
AR at Usy2>, Usy1>, and Synchr.
NO
AR at Usy1< and Usy2>
Functions
Comments
93