2.10

Command Processing

The SIPROTEC 4 7VK61 includes a command editing for initiating switching operations in the system. Control
can originate from four command sources:
• Local operation using the keypad on the local user interface of the device,
• Operation using DIGSI,
• Remote operation using a substation automation and control system (e.g. SICAM),
• Automatic functions (e.g. using binary inputs, CFC).
The number of switchgear devices that can be controlled is solely limited by the number of available and re-
quired binary inputs and outputs. For the output of control commands it has to be ensured that all the required
binary inputs and outputs are configured and provided with the correct properties.
If specific interlocking conditions are needed for the execution of commands, the user can program the device
with bay interlocking by means of the user-defined logic functions (CFC). The interlocking conditions of the
system can be injected via the system interface and must be allocated accordingly.
The procedure for switching resources is described in the SIPROTEC 4 System Description under Control of
Switchgear.
2.10.1

Control Authorization

2.10.1.1 Type of Commands

Commands to the Process
This type of commands are directly output to the switchgear to change their process state:
• Commands for the operation of circuit breakers (asynchronous; or synchronized through integration of the
synchronism check and closing control function) as well as commands for the control of isolators and earth
switches.
• Step commands, e.g. for raising and lowering transformer taps,
• Setpoint commands with configurable time settings, e.g. to control Petersen coils.
Device-internal Commands
These commands do not directly operate binary outputs. They serve for initiating internal functions, communi-
cating the detection of status changes to the device or for acknowledging them.
• Manual override commands for „manual update" of information on process-dependent objects such as an-
nunciations and switching states, e.g. if the communication with the process is interrupted. Manually over-
idden objects are marked as such in the information status and can be displayed accordingly.
• Flagging commands (for „setting") the data value of internal objects, e.g. switching authority (remote/local),
parameter switchovers, transmission blockages and deletion and presetting of metered values.
• Acknowledgment and resetting commands for setting and resetting internal buffers or data stocks.
• Information status commands to set/delete the additional „Information Status" item of a process object, such
as
– Acquisition blocking,
– Output blocking.
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009