Siemens Siprotec 7VK61 Manual page 289

Breaker management device
Hide thumbs Also See for Siprotec 7VK61:
Table of Contents

Advertisement

Addr.
Parameter
ϕB
2942
2943
I1>
2944
U1>
3401
AUTO RECLOSE
3402
CB? 1.TRIP
3403
T-RECLAIM
3403
T-RECLAIM
3404
T-BLOCK MC
3406
EV. FLT. RECOG.
3407
EV. FLT. MODE
3408
T-Start MONITOR
3409
CB TIME OUT
3410
T RemoteClose
3411A
T-DEAD EXT.
3425
AR w/ BackUpO/C
3430
AR TRIP 3pole
3431
DLC or RDT
3433
T-ACTION ADT
3434
T-MAX ADT
3435
ADT 1p allowed
3436
ADT CB? CLOSE
3437
ADT SynRequest
3438
T U-stable
3440
U-live>
3441
U-dead<
3450
1.AR: START
3451
1.AR: T-ACTION
3453
1.AR Tdead 1Flt
3454
1.AR Tdead 2Flt
3455
1.AR Tdead 3Flt
3456
1.AR Tdead1Trip
3457
1.AR Tdead3Trip
3458
1.AR: Tdead EV.
3459
1.AR: CB? CLOSE
3460
1.AR SynRequest
3461
2.AR: START
3462
2.AR: T-ACTION
3464
2.AR Tdead 1Flt
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
Function
C
Measurem.Superv
0 .. 359 °
Measurem.Superv
1A
0.05 .. 2.00 A
5A
0.25 .. 10.00 A
Measurem.Superv
2 .. 70 V
Autoreclosure
OFF
ON
Autoreclosure
YES
NO
Autoreclosure
0.50 .. 300.00 sec
Autoreclosure
0.50 .. 300.00 sec; 0
Autoreclosure
0.50 .. 300.00 sec; 0
Autoreclosure
with PICKUP
with TRIP
Autoreclosure
blocks AR
starts 3p AR
Autoreclosure
0.01 .. 300.00 sec
Autoreclosure
0.01 .. 300.00 sec
0.00 .. 300.00 sec; ∞
Autoreclosure
0.50 .. 300.00 sec; ∞
Autoreclosure
Autoreclosure
YES
NO
Autoreclosure
YES
Autoreclosure
NO
Autoreclosure
WITHOUT
RDT
DLC
0.01 .. 300.00 sec; ∞
Autoreclosure
Autoreclosure
0.50 .. 3000.00 sec
Autoreclosure
YES
NO
Autoreclosure
YES
NO
Autoreclosure
YES
NO
Autoreclosure
0.10 .. 30.00 sec
Autoreclosure
30 .. 90 V; ∞
Autoreclosure
Autoreclosure
Autoreclosure
2 .. 70 V
Autoreclosure
Autoreclosure
YES
NO
0.01 .. 300.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
Autoreclosure
0.01 .. 1800.00 sec
Autoreclosure
YES
NO
Autoreclosure
YES
NO
Autoreclosure
YES
NO
0.01 .. 300.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
Setting Options
Default Setting
340 °
0.05 A
0.25 A
20 V
ON
NO
3.00 sec
3.00 sec
1.00 sec
with TRIP
starts 3p AR
0.20 sec
3.00 sec
∞ sec
∞ sec
YES
YES
WITHOUT
0.20 sec
5.00 sec
NO
NO
NO
0.10 sec
48 V
30 V
YES
0.20 sec
1.20 sec
1.20 sec
0.50 sec
1.20 sec
0.50 sec
1.20 sec
NO
NO
NO
0.20 sec
1.20 sec
Appendix
A.7 Settings
Comments
Limit setting PhiB
Minimum value I1>
Minimum value U1>
Auto-Reclose function
CB ready interrogation at 1st trip
Reclaim time after successful AR
cycle
Reclaim time after successful AR
cycle
AR blocking duration after
manual close
Evolving fault recognition
Evolving fault (during the dead
time)
AR start-signal monitoring time
Circuit Breaker (CB) Supervision
Time
Send delay for remote close
command
Maximum dead time extension
AR with back-up overcurrent
3pole TRIP by AR
Dead Line Check or Reduced
Dead Time
Action time
Maximum dead time
1pole TRIP allowed
CB ready interrogation before re-
closing
Request for synchro-check after
3pole AR
Supervision time for dead/ live
voltage
Voltage threshold for live line or
bus
Voltage threshold for dead line or
bus
Start of AR allowed in this cycle
Action time
Dead time after 1phase faults
Dead time after 2phase faults
Dead time after 3phase faults
Dead time after 1pole trip
Dead time after 3pole trip
Dead time after evolving fault
CB ready interrogation before re-
closing
Request for synchro-check after
3pole AR
AR start allowed in this cycle
Action time
Dead time after 1phase faults
289