Description; Information List - Siemens Siprotec 7VK61 Manual

Breaker management device
Hide thumbs Also See for Siprotec 7VK61:
Table of Contents

Advertisement

Functions
2.10 Command Processing

2.10.2.1 Description

Operation via integrated control panel
Using the navigation keys ▲, ▼,
selected. After entering a password, a new window is displayed where multiple control options (ON, OFF,
ABORT) are available using the ▼ and ▲ keys. Then a safety query appears. Only after repeated confirmation
using the E
NTER
process is aborted. Cancellation via the E
or during breaker selection.
Operation using DIGSI
Switchgear devices can be controlled via the operator interface with a PC using the DIGSI software. The pro-
cedure is described in detail in the SIPROTEC 4 System Description (Control of Switchgear).
Operation using the System Interface
Control of switchgear can be performed via the serial system interface and a connection to the substation
control and protection system. A prerequisite for this is that the required peripherals physically exist in the
device and the substation. Also, specific settings to the serial interface must be made in the device (see SIPRO-
TEC 4 System Description ).

2.10.2.2 Information List

No.
Information
-
Breaker
-
Breaker
-
Disc.Swit.
-
Disc.Swit.
-
EarthSwit
-
EarthSwit
-
Brk Open
-
Brk Close
-
Disc.Open
-
Disc.Close
-
E Sw Open
-
E Sw Cl.
-
Q2 Op/Cl
-
Q2 Op/Cl
-
Q9 Op/Cl
-
Q9 Op/Cl
-
Fan ON/OFF
-
Fan ON/OFF
31000
Q0 OpCnt=
31001
Q1 OpCnt=
31002
Q2 OpCnt=
31008
Q8 OpCnt=
31009
Q9 OpCnt=
176
,
, the control menu can be accessed and the switchgear to be operated
key is the command action performed. If this enabling does not occur within one minute, the
SC
Type of In-
formation
CF_D12
DP
CF_D2
DP
CF_D2
DP
IntSP
IntSP
IntSP
IntSP
IntSP
IntSP
CF_D2
DP
CF_D2
DP
CF_D2
DP
VI
VI
VI
VI
VI
key is possible at any time before the control command is issued
Breaker
Breaker
Disconnect Switch
Disconnect Switch
Earth Switch
Earth Switch
Interlocking: Breaker Open
Interlocking: Breaker Close
Interlocking: Disconnect switch Open
Interlocking: Disconnect switch Close
Interlocking: Earth switch Open
Interlocking: Earth switch Close
Q2 Open/Close
Q2 Open/Close
Q9 Open/Close
Q9 Open/Close
Fan ON/OFF
Fan ON/OFF
Q0 operationcounter=
Q1 operationcounter=
Q2 operationcounter=
Q8 operationcounter=
Q9 operationcounter=
C53000-G1176-C159-3, Release date 05.2009
Comments
SIPROTEC, 7VK61, Manual