Appendix
A.7 Settings
Addr.
Parameter
3465
2.AR Tdead 2Flt
3466
2.AR Tdead 3Flt
3467
2.AR Tdead1Trip
3468
2.AR Tdead3Trip
3469
2.AR: Tdead EV.
3470
2.AR: CB? CLOSE
3471
2.AR SynRequest
3472
3.AR: START
3473
3.AR: T-ACTION
3475
3.AR Tdead 1Flt
3476
3.AR Tdead 2Flt
3477
3.AR Tdead 3Flt
3478
3.AR Tdead1Trip
3479
3.AR Tdead3Trip
3480
3.AR: Tdead EV.
3481
3.AR: CB? CLOSE
3482
3.AR SynRequest
3483
4.AR: START
3484
4.AR: T-ACTION
3486
4.AR Tdead 1Flt
3487
4.AR Tdead 2Flt
3488
4.AR Tdead 3Flt
3489
4.AR Tdead1Trip
3490
4.AR Tdead3Trip
3491
4.AR: Tdead EV.
3492
4.AR: CB? CLOSE
3493
4.AR SynRequest
3501
FCT Synchronism
3502
Dead Volt. Thr.
3503
Live Volt. Thr.
3504
Umax
3507
T-SYN. DURATION
3508
T SYNC-STAB
3509
SyncCB
3510
Op.mode with AR
3511
AR maxVolt.Diff
3512
AR maxFreq.Diff
3513
AR maxAngleDiff
3515A
AR SYNC-CHECK
3516
AR Usy1<Usy2>
3517
AR Usy1>Usy2<
3518
AR Usy1<Usy2<
290
Function
C
0.01 .. 1800.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
Autoreclosure
0.01 .. 1800.00 sec
Autoreclosure
YES
NO
Autoreclosure
YES
NO
Autoreclosure
YES
NO
0.01 .. 300.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
Autoreclosure
0.01 .. 1800.00 sec
Autoreclosure
YES
NO
Autoreclosure
YES
NO
Autoreclosure
YES
NO
0.01 .. 300.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
Autoreclosure
0.01 .. 1800.00 sec
Autoreclosure
YES
NO
Autoreclosure
YES
NO
Sync. Check
ON
OFF
ON:w/o CloseCmd
Sync. Check
1 .. 100 V
Sync. Check
20 .. 125 V
Sync. Check
20 .. 140 V
0.01 .. 600.00 sec; ∞
Sync. Check
Sync. Check
0.00 .. 30.00 sec
Sync. Check
(Setting options depend
on configuration)
Sync. Check
with T-CB close
w/o T-CB close
Sync. Check
1.0 .. 60.0 V
Sync. Check
0.03 .. 2.00 Hz
Sync. Check
2 .. 80 °
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Sync. Check
YES
NO
Setting Options
Default Setting
1.20 sec
0.50 sec
∞ sec
0.50 sec
1.20 sec
NO
NO
NO
0.20 sec
1.20 sec
1.20 sec
0.50 sec
∞ sec
0.50 sec
1.20 sec
NO
NO
NO
0.20 sec
1.20 sec
1.20 sec
0.50 sec
∞ sec
0.50 sec
1.20 sec
NO
NO
ON
5 V
90 V
110 V
1.00 sec
0.00 sec
None
w/o T-CB close
2.0 V
0.10 Hz
10 °
YES
NO
NO
NO
C53000-G1176-C159-3, Release date 05.2009
Comments
Dead time after 2phase faults
Dead time after 3phase faults
Dead time after 1pole trip
Dead time after 3pole trip
Dead time after evolving fault
CB ready interrogation before re-
closing
Request for synchro-check after
3pole AR
AR start allowed in this cycle
Action time
Dead time after 1phase faults
Dead time after 2phase faults
Dead time after 3phase faults
Dead time after 1pole trip
Dead time after 3pole trip
Dead time after evolving fault
CB ready interrogation before re-
closing
Request for synchro-check after
3pole AR
AR start allowed in this cycle
Action time
Dead time after 1phase faults
Dead time after 2phase faults
Dead time after 3phase faults
Dead time after 1pole trip
Dead time after 3pole trip
Dead time after evolving fault
CB ready interrogation before re-
closing
Request for synchro-check after
3pole AR
Synchronism and Voltage Check
function
Voltage threshold dead line / bus
Voltage threshold live line / bus
Maximum permissible voltage
Maximum duration of synchro-
nism-check
Synchronous condition stability
timer
Synchronizable circuit breaker
Operating mode with AR
Maximum voltage difference
Maximum frequency difference
Maximum angle difference
AR at Usy2>, Usy1>, and Synchr.
AR at Usy1< and Usy2>
AR at Usy1> and Usy2<
AR at Usy1< and Usy2<