Pre-fault and post-fault times will be included. If the binary input time is set for ∞, then the length of the record
equals the time that the binary input is activated (static), or the MAX. LENGTH setting in address 410, which-
ever is shorter.

2.1.6.3 Settings

Addresses which have an appended "A" can only be changed with DIGSI, under Additional Settings.
Addr.
Parameter
402A
WAVEFORMTRIGGE
R
403A
WAVEFORM DATA
410
MAX. LENGTH
411
PRE. TRIG. TIME
412
POST REC. TIME
415
BinIn CAPT.TIME

2.1.6.4 Information List

No.
Information
-
FltRecSta
4
>Trig.Wave.Cap.
30053
Fault rec. run.
SIPROTEC, 7VK61, Manual
C53000-G1176-C159-3, Release date 05.2009
Setting Options
Save w. Pickup
Save w. TRIP
Start w. TRIP
Fault event
Pow.Sys.Flt.
0.30 .. 5.00 sec
0.05 .. 0.50 sec
0.05 .. 0.50 sec
0.10 .. 5.00 sec; ∞
Type of In-
formation
IntSP
Fault Recording Start
SP
>Trigger Waveform Capture
OUT
Fault recording is running
Default Setting
Save w. Pickup
Waveform Capture
Fault event
Scope of Waveform Data
2.00 sec
Max. length of a Waveform
Capture Record
0.25 sec
Captured Waveform Prior to
Trigger
0.10 sec
Captured Waveform after Event
0.50 sec
Capture Time via Binary Input
Comments