INSTALLER
Fit the feet provided into the holes in the bottom of the storage
cylinder and adjust as necessary to compensate for any
unevenness in the floor.
The casing and insulation can be removed to facilitate access
into the place of installation. To do so, proceed as follows.
− Remove the plug (2). Unscrew the two fixing screws and
remove the top insulation section (3).
− Remove the protective fitting plugs (4).
− Unzip the plastic cover (5).
− Cut the straps (6)
− Remove the insulation shells (7).
Reverse the above steps to fit the insulation again.
7
5
9
Make sure that the insulation shells (7) are securely fixed in
place by straps before fitting the plastic cover. Use a strap
wrench if necessary.
9
Wear suitable personal protective equipment and use
suitable safety devices.
0
Do not dispose of packaging material into the environment,
or leave it within the reach of children, since it can become
a potential hazard. Dispose of packaging material in
compliance with applicable legislation.
17
2
3
4
6

12 PLACE OF INSTALLATION

R
7200 V Plus storage cylinders can be installed in any
room where there is no specific requirement for an electrical
protection rating higher than IP X0D.
9
Respect the minimum specified installation distances to
ensure correct installation and access for maintenance.
13 INSTALLATION IN OLDER SYSTEMS AND SYSTEMS
REQUIRING MODERNISATION
When installing
R
7200 V Plus storage cylinders in old systems
or systems requiring modernisation, always perform the
following checks.
− Make sure that the system is fitted with safety and
control devices in accordance with applicable legislation
and standards
− Make sure that the central heating circuit has been
flushed out to remove all sludge and lime scale, and has
been vented and seal tested
− Make sure that a suitable water treatment system is
installed if the quality of the supply/recirculation water
so demands. (Refer to the reference values listed in the
table alongside.)
REFERENCE VALUES
pH
Electrical conductivity
Chlorine ions
Sulphuric acid ions
Total iron
Alkalinity M
Total hardness
Sulphur ions
Ammonia ions
Silicon ions
13
INSTALLER
6-8
less than 200 μS/cm (25°C)
less than 50 ppm
less than 50 ppm
less than 0.3 ppm
less than 50 ppm
less than 35°F
none
none
less than 30 ppm