NOTE: If no value is programmed and DHCP is used, the DHCP server will configure the address. If an address is pro-
grammed and DHCP is used, the programmed address will be used instead of the DHCP address.
[008] Backup Ethernet DNS IP
Default (000.000.000.000)
Enter the IP address for DNS server 2. Format is 4 fields, each field is a 3-digit decimal. Valid range: 000-255.
NOTE: If no value is programmed and DHCP is used, the DHCP server will assign this value. If an address is programmed
and DHCP is used, the programmed address will be used instead of the DHCP address.
[009] Language
Default (01)
Opt
01
English
02
Spanish
03
Portuguese
04
French
05
Italian
06
Dutch
07
Polish
08
Czech
NOTE: Programming this section with an invalid language will default to English (01).
NOTE: After programming this section, perform a Default Language in section [999][11] to have programmable labels avail-
able in the selected language.

Programming Options

[010] System Toggle Options 3
[1] 2-Way Audio Over Cellular. Default (OFF)
ON: 2-Way Audio Over Cellular is enabled.
OFF: 2-Way Audio Over Cellular is disabled.
[2] Visual Verification. Default (OFF)
ON: Visual verification is enabled.
OFF: Visual verification is disabled.
[3] Video On Demand. Default (OFF)
ON: Video On Demand is enabled.
OFF: Video On Demand is disabled.
[4] Receiver Group. Default (OFF)
ON: Receiver Group is enabled.
OFF: Receiver Group is disabled.
NOTE: Enable this option when visual verification needs to be sent to more than one receiver.
NOTE: Auto-Routing must be enabled in section [300] of the Neo panel.
[5] - [8] Reserved.
[011] Installer Code
Default (CAFE)
Program the installer code for the communicator module. The installer code will be required when programming the com-
municator module. Valid range: 0000 - FFFF.
[012] DLS Incoming Port
Default (0BF6/3062)
The DLS incoming local port (listening port) is the port DLS IV will use when connecting to the communicator. If a router or
gateway is used, it must be programmed with a transmission control protocol (TCP) port forward for this port to the com-
municator module IP address. Valid range: 0000 - FFFF.
Language
Opt
Language
09
Finnish
10
German
11
Swedish
12
Norwegian
13
Danish
14
Hebrew
15
Greek
16
Turkish
Opt
Language
17
Not Used
18
Croatian
19
Hungarian
20
Romanian
21
Russian
22
Bulgarian
23
Latvian
24
Lithuanian
23
Opt
Language
25
Ukrainian
26
Slovakian
27
Serbian
28
Estonian
29
Slovenian
30-99 Reserved