EN50136-1:2012 AnnexD Table D.6
EN50136-1:2012 Table 1
EN50136-1:2012 Table 4
EN50136-1:2012 Table 5
EN50136-1:2012 Table 6
EN50136-2:2013 Table 1
EN50136-2:2013 Table 2
EN50136-2:2013 Table 3
SIMPLIFIED EU DECLARATION OF CONFORMITY
Hereby, Tyco Safety Products Canada Ltd declares that the radio equipment type is in compliance with Directive 2014/53/EU. The full text of the EU declar-
ationsof conformityfor the modelsmentioned below are available at the following internet addresses:
TL2803G(R)E-EU - http://dsc.com/pdf/1605003
3G2080(R)E- EU - http://dsc.com/pdf/1605004
Frequency Band
EGSM900 890.0MHz- 914.8MHz
EGSM900 880.2MHz-889.8MHz
DCS1800 1710.2MHz-1784.8MHz
WCDMA(Band VIII) 882.4MHz- 912.6MHz
WCDMA2100 (Band I) 1922.4MHz- 1977.6MHz Class3 (0.25W) @ 900/2100MHz, WCDMA
OnlymodelsTL2803GRE-EU, TL2803GE-EU, 3G2080RE-EU, 3G2080E-EU are CEcompliant.
European single point of contact: Tyco SafetyProducts, Voltaweg 20, 6101 XKEcht, Netherlands
UL/ULC Installation Requirements
NOTE: For equipment used at the protected premises and intended to facilitate IP communications (hubs, routers, NIDs, DigitalSubscriber Line (DSL), cable
modems), 24 hour backup power isrequired. Where such cannot be facilitated, a secondary(back-up) communication channelisrequired.
Domain Name Service (DNS) programming is not permitted in UL1610 listed systems.
Technical Specifications
The input voltage to the Communicator can be drawn fromthe UnderwritersLaboratories/UnderwritersLaboratoriesCanada (UL/ULC) listed controlpanel.
Notes for using Private, Corporate, and High Speed Data Networks:
Network access and domain access policies shall be set to restrict unauthorized network access, and spoofing or Denial of Service (DoS) attacks. Select an
Internet Service Provider (ISP) that has redundant servers/systems, back-up power, routers with firewalls enabled, and methods to identify and protect
against DoSattacks(e.g., via spoofing).
Notes for using Public Switched and Cellular Data Networks:
Communication channels shall be facilitated such that the communicator will restrict unauthorized access, which could otherwise compromise security. The
communicator shallbe located in a secured area.
• For ULC Residential Fire and Burglary applications the TL2803G(R)E/3G2080(R)E/TL280(R)E/LE2080(R)/TL280LE(R) can be used as primary com-
munication channel via either cellular or Ethernet or as a back-up in conjunction with the Digital Alarm Communicator Transmitter (DACT). Test transmission
every24 hoursshallbe enabled on each channel.
• For ULC Commercial Fire and Burglary applications the TL2803G(R)E/3G2080(R)E/TL280(R)E/LE2080(R)/TL280LE(R) can be used as a passive
communication module with the following securitylevels:
P1 (each channelcellular or Ethernet isindependent)
l
P2 (cellular and Ethernet in back-up configuration, panelsection [851][005] toggle option [5] OFF).
l
P3 (cellular and Ethernet in redundant configuration, panelsection [851][005] toggle option [5] ON).
l
The communicator can also be used as an active communication system with the security levels A1-A4 (each channel cellular or Ethernet independent or
together in a back-up/redundant configuration). For active line security systems AES128 bit encryption shall be enabled (at the monitoring station receiver)
and the supervision heartbeat rate shallbe set as 90 seconds (panelsection [851][004] = 005A/90). The supervision window at the SignalReceiver Center
(SRC)'sreceiver shallbe programmed asmaximumof 180 (00B4/180) seconds.
NOTE: For ULC commercialfire passive communication, encryption shallbe enabled,
• For UL Residential Fire and Burglary applications the TL2803G(R)E/3G2080R/TL280(R)E/LE2080(R)/TL280LE(R) can be used as the primary com-
munication channelvia either cellular or Ethernet, or asa back-up in conjunction with the DACT (30 daytest transmission isrequired on each channel).
• For UL Commercial Burglary applications the TL2803G(R)E/ 3G2080R / TL280(R)E / LE2080(R) / TL280LE(R) can be used as dual signalling line
communication system(cellular and Ethernet channelsused in redundant configuration), standard line securityand asencrypted line security.
• The supervision heartbeat shall be enabled (panel section [851][005] toggle option [1] (Ethernet) and/or toggle option [2] (cellular) shall be ON), toggle
option [3] (supervision type) shall be ON and the supervision heartbeat rate shall be selected as 135 (0087/135) seconds. Option [004] = 0087. The super-
vision window at the supervising station shall be maximum 200 (00C8/200) seconds. For encrypted line security systems the encryption AES128 bit shall be
enabled at the monitoring station receiver.
• For UL Commercial Burglary installations, the TL2803G(R)E/3G2080 (R)E/TL280 (R)E/LE2080 (R)/TL280LE(R) is listed as a primary (sole) com-
munication means (heartbeat must be enabled) or for supplementary (back-up) use in conjunction with a Plain Old Telephone Service (POTS) line dialer.
When the heartbeat transmission over the Ethernet or cellular network is enabled, using the TL2803G(R)E/3G2080(R)E/TL280(R)E with a compatible con-
trolunit listed for standard/encrypted line security, it can provide line securityfor the alarmsystemover the primaryline.
• The TL2803G(R)E/3G2080(R)E/TL280(R)E/LE2080(R)/TL280LE(R) is also suitable to be used with a compatible control unit listed for dual line security
transmission when used in conjunction with a DACT or a Public Switched Data Network (PSDN) transmitter, where the PSDN provides the line security and is
the primaryline. In thismode, alarmsignalsare required to be sent simultaneouslyover both communication methods.
I2 (use AES-128 encryption)
Use single communication path for models 3G2080 (R)E- EU (cellular
network), TL280 (R)E (Ethernet port) and two communication paths for
modelTL2803G(R)E-EU (cell/Ethernet).
ATSfailure reported to ARC
ATS failure reported to AS (DSC compatible control panel
HS2128/HS2064/HS2032/HS2016)
There isno recording of availabilityfailure
No logging function provided
No memoryprovided for logging function
ATSfailure reported to ARC
Maximum Power
Class4 (2W) @ 900MHz, GSM
Class1(1W) @ 1800MHz, GSM
ClassE2 (0.5W) @ 900MHz, EDGE
ClassE2 (0.4W) @ 1800MHz, EDGE