U M C 1 0 0 . 3 U N I V E R S A L M O T O R C O N T R O L L E R T E C H N I C A L D E S C R I P T I O N
86

Control Function Actuator 1 - 4

Use this function in a feeder that requires the operation of an actuator that opens/closes e.g. a valve. Please note that the actuator
operation mode is not able to keep a valve at a certain setpoint.
The voltage dip function is not supported and checkback via DIO is not supported in these control functions.
Set the following parameters as listed here:
• Inv DI start input = No
• Inv DI stop input = No
• Inching DI start input (Jog) = Yes
• Multifunction 0/1 = Off
• Checkback: Current or Simulation (test purposes only)
• Adjust Time Limit Actuator
UMC-
PAN
Comm.
interface
0V
Control function = Actuator 2 (Basic circuit)
The control functions Actuator 1, 2, 3 and 4 provide different use of and reaction to the limit switches "Closed" and "Open" as well
as the torque switches. The switches must be connected in a predefined manner to DI0, DI1 and DI3.
Optionally terminals named 24VDC Out (12) or DO2 can be used as a fault output
GND
Contactor
(24VDC)
Supply
(e.g. 230VAC)
24VDC
DO3
DOC DO0
I
UMC100
Lim
DI0
DI1
DI2
Limit
Limit
Closed
Open
24VDC
L1, L2, L3
K1
K2
DO1
DO2
3
DI3
DI4 DI5
Close
k1
Open
Torque
Open/
Closed
M
K1=Open
K2=Close
k2