Connecting More Than One Expansion Module; Connecting Contactors; Actual Abb Contactors - All Currents For 230 V Ac (Extract): - ABB UMC100.3 Manual

Univeral motor controller
Hide thumbs Also See for UMC100.3:
Table of Contents

Advertisement

U M C 1 0 0 . 3 U N I V E R S A L M O T O R C O N T R O L L E R T E C H N I C A L D E S C R I P T I O N
22

Connecting more than one expansion module

To connect several expansion modules to the UMC100.3 use the UMCIO-CAB cable to connect the first module with the UMC. And
use the IOIO-CAB cable to connect the first module with the second module and so on. The module order does not matter.

Connecting Contactors

Actual ABB contactors - all currents for 230 V AC (Extract):

Contactor type
B6S-30-10-2.8
1)
AF09Z - AF38Z
AF40 - AF65
AF80 - AF96
AF116 - AF146
AF190, AF205
AF265 - AF370
AF400, AF460, AF580, AF750
1)
The contactor B6S-30-10-2.8 (24 V DC) is recommended as interface contactor due to its internal spark suppression.
Spark suppression is necessary for all types except the AF types to maintain a reasonable service life.
24VDC/0V
K
1
On
2
Off-N
3
COM
DOC DO0
DO1
UMC100
Connection of contactors with electronic interface (AF types)
to the UMC100.3
*) Slide switch on the left side to position 'PLC' (up)
Inrush current [A]
0.01
0.07
0.11
0.17
0,56
0,96
1.67
4.15
L1, L2, L3
230VAC
*)
k1
DO2
3
Holding current [A]
0.01
0.007
0.017
0.017
0.026
0.03
0.08
0.05
Inrush power [VA]
Holding power [VA]
2.4
16
25
40
130
220
385
955
2.4
1.7
4
4
6
7
17.5
12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents