Use the LCD panel as automatic parameter backup storage

All settings can also be stored in the operator panel automatically. This is interesting in case of a UMC100.3 replacement. This new
function requires that UMC and operator panel have revision.
UMC100.3
Operator panel
This function is not supported in the UMC100.3 ATEX and UMC100.3 ATEX with conformal coating!

The function stores

All UMC100.3 parameters for configuration
Custom application
Fieldbus address
Address check
I/O Data profile
DeviceNet communication baudrate
MODBUS communication data (baudrate, frame format, timeout)
Retrofit
Parameter for Ethernet/IP

It does not store

Counter values (Number of trips, thermal trips, starts, emergency starts, operating hours, stand still hours, energy)
All data related to the thermal memory (motor model)
Historical data from function block NON_VOL_SR_FF
This function is by default deactivated (Auto Save = OFF).

Activation of auto save function

After configuration of the UMC100.3 the auto save function must be enabled. The activation is done by setting the parameter "Ena-
ble Auto Save = ON" in the LCD panel menu.
All settings as mentioned above are now uploaded to the operator panel, the green LED on the UMC100.3 is flashing. This
transfer takes a few minutes (~ 3 min.). After successful writing a disk symbol on the LCD-Panel indicates that this function is
activated.
From now on changed parameters are continuously stored into the LCD-Panel. Writing is indicated by the flashing disk symbol.
At the next UMC100.3 startup a LCD-Panel with saved parameters is expected.
Deactivation of auto save function
With an activated parameter "Enable Auto Save = ON" the UMC100.3 always expects a valid LCD panel at startup. To deactivate this
function:
Set the parameter "Enable Auto Save = OFF" with the LCD-Panel
The parameters stored in the LCD-Panel are deleted.
During the next startup the UMC100.3 use the internal stored parameters.
Replacing a UMC100.3 or behavior during power on, if auto save is enabled
UMC100.3: The green LED is blinking during the data transfer from LCD panel into UMC100.3.
LCD-Panel: In the main menu, in the Status line (first line) the text message "Download to UMC" is blinking. When the download to
UMC100.3 is finished the normal text is displayed and a disk symbol is activated in the first line on the left side.
Replacing operator panel UMC100-PAN
UMC100.3: The green LED is blinking during the data transfer to the LCD-Panel.
LCD-Panel: In the main menu, in the Status line (first line) the text message "Upload to LCD panel" is blinking. When the upload to
LCD-Panel is finished the normal text is displayed and a disk symbol is activated in the first line on the left site.
Parameter setting for warning "LCD panel missing"
A warning "LCD panel missing" can be enabled or disabled. The parameter is located in menu Display -> En Auto Save React. The de-
fault value is ON. If the function "Enable Auto Save" is activated and the LCD-Panel is disconnected later, a warning is generated
"LCD panel missing". This warning is also sent via fieldbus/network in the Diagnosis Byte 4 Bit 0.
Do not remove the LCD panel or power off the UMC100.3 in following cases
The text message "Upload to LCD panel" is blinking
The text message "Download to UMC" is blinking
The disk symbol is blinking.
SW: 3.07 check via operator panel Maintenance/service -> UMC100 SW version
SW: 4.0