U M C 1 0 0 . 3 U N I V E R S A L M O T O R C O N T R O L L E R T E C H N I C A L D E S C R I P T I O N
50

Function Overview

Protection Function voltage
Overvoltage:
The highest value of the three phases is above a given
threshold.
The warning - and trip thresholds as well as the according
delays can be set.
Undervoltage:
The lowest value of the three phases is below a given
threshold.
The warning - and trip thresholds as well as the according
delays can be set.
Voltage Dip:
Low voltage situation which requires an
autonomous load sheeding
handling should take place in the UMC.
Phase loss:
In opposite to the current based phase loss protection
function this function detects a missing phase also in the
case the motor is stopped.
A warning / trip can be signalled before the motor is actually
started i.e. to detect a blown fuse.
Voltage imbalance:
This function can be used to detect smaller voltage
imbalances between the phases.
Warning - and trip thresholds as well as warning - and trip
delays can be set.
Total harmonic distortion:
This function measures harmonic distortions in the
connected mains.
Overload:
The active power drawn by the motor is too high. The
warning - and trip thresholds as well as the according delays
can be set.
Underload:
The active power drawn by the motor is too low. The
warning - and trip thresholds as well as the according delays
can be set.
Cos phi:
A measure of the phase angle between voltage and current.
The warning - and trip thresholds as well as the according
delays can be set.
When active
Motor running
Motor stopped
Not in test position
Motor running
Motor stopped
Not in test position
After motor start
Not in test position
Motor running
Motor stopped
Not in test position
Motor running
Motor stopped
Not in test position
Motor running
Motor stopped
Not in test position
After load start
Not in test position
After load start
Not in test position
After load start
Not in test position
Available Options:
Warning/Trip/Off/Other
Trip, Warning, Off
Trip, Warning, Off
Reaction depends on Dip
duration.
Trip, Warning, Off
Trip, Warning, Off
Warning
Trip, Warning, Off
Trip, Warning, Off
Trip, Warning, Off
Automatic Fault
Reset Possible
-
-
-
-
Yes, see parameter
'Fault auto reset'
-
-
-
-