PA R A M E T E R S A N D D ATA S T R U C T U R E S O N A F I E L D B U S

Function Block Related Parameters

Aux Input Block

In the standard built-in applications the inputs of this function block are connected to the digital inputs of the DX1xx module (see
section 'Using Expansion Modules').
Parameter
Parameter Name
Number
51 - 56
Aux inp 1-6 ack mode
57 - 61
Aux Inp 1-6 reaction
63/64
Aux Inp 1-6 message
65/66
Line 1/Line 2
67/68
69/70
71/72
73/74
75 - 80
Aux Inp 1-6 delay
Description, Explanation
Definition of the fault reset behavior
Definition of the input function
NC: Normally closed
NO: Normally open
Message text line 1 and line 2
Input delay time in multiples of 100ms
Options
Manual Reset (0)
Auto Reset (1)
Disabled (0)
Fault (NC) Motor in On/Off (1)
Fault (NO) Motor in On/Off (2)
Fault (NC) Motor in On (3)
Fault (NO) Motor in On (4)
Warning (NC) Motor in On/Off (5)
Warning (NO) Motor in On/Off (6)
Warning (NC) Motor in On (7)
Warning (NO) Motor in On (8)
Free text with 8 characters for
each line. Default: „Aux DIx" with
x=1...6
0 ... 255 in multiples of 0.1s
Example: A value of 5 means
500ms
137
Adjustable via
All
All
DTM, UMC100-PAN
All excluding GSD-
PDQ22