Advertisement

U M C 1 0 0 . 3 U N I V E R S A L M O T O R C O N T R O L L E R T E C H N I C A L D E S C R I P T I O N
132
IO Module Parameters

DX111-FBP.0 / DX122-FBP.0 Parameters

Parameter
Parameter
Number
Name
8
Missing Module
Reaction
1
DX1xx Enabled
151
DX1xx DI delay
152
DX1xx AO type
153
DX1xx AO error
reaction
Description, Explanations
Defines if the UMC creates a fault or a warning in case of a
missing IO module.
Specify if the module is connected to UMC
Input delay in ms assuming a line frequency of 50Hz
Hardware type of the analogue output on the DX1xx
module.
Reaction if the AO detects a short-circuit or wire break
condition.
Options
Error (0)
Warning (1)
Off (0), On (1)
DX111: 3...200ms
Values are rounded up to the
next multiple of 3.
E.g.:
7,8,9 -> 9 ms delay
In addition to the software delay
a fix hardware delay of about
4ms must be considered.
DX122: 3...200ms
Values are rounded to the next
multiple of 10. Values below 20
are rounded up to 20.
E.g.:
3...20: 20 ms delay
81...90: 90 ms delay
0 - 20mA (0),
4 - 20mA (1),
0 - 10mA (2),
0 - 10V (3)
Disabled (0),
Trip (1),
Warning (2)
Adjustable via
All
All
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22
All excluding
GSD-PDQ22