Electrical Wiring; Precautions When Connecting Electrical Wiring; Opening The Switch Box - Daikin VAM350J7VEB Installer And User Reference Manual

Heat reclaim ventilation unit
Hide thumbs Also See for VAM350J7VEB:
Table of Contents

Advertisement

Models 350~1000
Name Plate
a
b
c
a
Models 1500+2000
d
a
Aluminium tape (field supply)
b
Insulation material (field supply)
c
Duct joint (accessories)
d
Slope minimum 1:50
e
Supply air
f
Room air
6.5

Electrical wiring

INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
WARNING
▪ All wiring MUST be performed by an authorised
electrician and MUST comply with the applicable
legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical
construction
MUST
legislation.
6.5.1
Precautions when connecting electrical
wiring
DANGER: RISK OF ELECTROCUTION
WARNING
If NOT factory installed, a main switch or other means for
disconnection, having a contact separation in all poles
providing full disconnection under overvoltage category  III
condition, MUST be installed in the fixed wiring.
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
d
c
e
e
f
comply
with
the
applicable
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable
legislation.
▪ All field wiring MUST be performed in accordance with
the wiring diagram supplied with the product.
▪ NEVER squeeze bundled cables and make sure they
do NOT come in contact with the piping and sharp
edges. Make sure no external pressure is applied to the
terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
▪ Make sure to install the required fuses or circuit
breakers.
▪ Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
▪ When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high
frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
WARNING
▪ After finishing the electrical work, confirm that each
electrical component and terminal inside the electrical
components box is connected securely.
▪ Make sure all covers are closed before starting up the
unit.
NOTICE
If the power supply has a missing or wrong N-phase,
equipment will break down.
NOTICE
Do NOT install a phase advancing capacitor, because this
unit is equipped with an inverter. A phase advancing
capacitor will reduce performance and may cause
accidents.
6.5.2

Opening the switch box

CAUTION
Before opening the cover, be sure to turn off the power
switches of the main units and other devices connected to
the main units.
▪ Remove the screws that secure the cover and open the
switch box.
▪ Secure the power supply cable and the control wire
with a tie wrap, as shown in the figures.
6 Installation
Installer and user reference guide
17