Daikin VAM350J7VEB Installer And User Reference Manual page 37

Heat reclaim ventilation unit
Hide thumbs Also See for VAM350J7VEB:
Table of Contents

Advertisement

Linear control
Measuring
Every 5 minutes
Evaluation
Every 30 minutes
(average of 6
measurements)
Trigger
Linear control (minutes)
value
UH
H
CO₂ ppm (1)
≥1450
30
1300~1450
20
10
1150~1300
10
20
1000~1150
30
850~1000
20
700~850
10
550~700
400~550
0~400
(1)
CO₂ parts per million
UH
Ultra high
H
High
L
Low
Example
When the sensor measures 900 ppm in linear control, the unit runs
in high mode for 20 minutes and the next 10 minutes in low mode,
then measures again.
Essential wiring
See
"6.5.2 Opening the switch box" on page 17
manual that is delivered with the CO
To remove the components
c
a
d
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
Fixed control
Every 20 minutes
Every 20 minutes
Fixed control
L
Mode A
Mode B
UH
UH
UH
UH
H
H
H
H
10
H
L
20
L
L
30
L
L
20
L
stop
10
L
stop
and the installation
sensor.
2
d
e
d
c
d
b
g
f
a
Hinge mechanism
b
Service cover
c
Heat exchange element
d
Air filter
e
Heat exchange element rail
f
Screw 1
g
Screw 2
1 Open the service cover hinge by loosening the screw.
2 Remove the service cover.
3 Remove the 2 heat exchange elements and the 4 air filters.
4 Remove the screw from the right heat exchange element rail.
5 Remove the heat exchange element rail.
6 Loosen screw 2, and remove screw 1.
INFORMATION
Use a crosshead screwdriver with a shank of more than
65 mm and a total length of less than 120 mm.
To install the CO2 sensor
b
a
Screw 1
b
Screw 2
c
Damper motor wire
d
Clamp
1 Use the 2 screws to install the CO₂ sensor. See
components" on page 37
for details.
NOTICE
Make sure that the damper motor wire is NOT trapped
under the kit.
8 Configuration
c
a
d
"To remove the
Installer and user reference guide
37