To Install The Duct Joints; Preparing Electrical Wiring; Wiring Connection; Component Electrical Specifications - Daikin VAM350J7VEB Installer And User Reference Manual

Heat reclaim ventilation unit
Hide thumbs Also See for VAM350J7VEB:
Table of Contents

Advertisement

2 Attach the optional mounting plate (EKMPVAM) on top of the
plate connecting the 2 units.
3 Attach the optional adapter PCB (KRP2A51) in the installation
box (KRP1BA101).
4 Follow the installation instructions provided with the option kits
(BRP4A50A, KRP2A51 and KRP1BA101).
5 Guide the PCB wire through the dedicated holes and attach it
as instructed in
"6.5.2 Opening the switch box" on
6 Attach the options to the optional mounting plate, as shown in
the figure.
7 After the wires are connected, fasten the switch box cover.
5.3.2

To install the duct joints

1 Position the duct joints over the duct holes.
2 Secure the duct joints with the provided screws (accessories).
2
Model
Number of provided
screws
350
500
650
800
1000
1500
2000
5.4

Preparing electrical wiring

5.4.1

Wiring connection

WARNING
A main switch or other means for disconnection, having a
contact separation in all poles, MUST be incorporated in
the fixed wiring in accordance with the applicable
legislation.
You can use a single switch to supply power to units on the same
system. However, branch switches and branch circuit breakers
MUST be selected carefully.
Fit the power supply wiring of each unit with a switch and fuse as
shown in the drawing below.
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
page 17.
1
Number of provided
duct joints
16
4× Ø200 mm
16
4× Ø200 mm
24
4× Ø250 mm
24
4× Ø250 mm
24
4× Ø250 mm
48
8× Ø250 mm
48
8× Ø250 mm
Complete system example
a
c
d
b
e
b
e
a
VRV outdoor unit
b
VRV indoor unit
c
Power supply
d
Main switch
e
Controller
5.4.2

Component electrical specifications

Model
350
500
Power supply
50 Hz
60 Hz
MCA (A)
1.56
2.08
MFA (A)
16
16
Fan motor
P (kW)
0.08×2
0.08×2
FLA (A)
0.62×2
0.83×2
MCA
Minimum Circuit Amps
MFA
Maximum Fuse Amps
P
Motor Rated Load
FLA
Full Load Amps
NOTICE
When using residual current operated circuit breakers,
make sure to use a high speed type 300 mA rated residual
operating current.
NOTICE
The power supply MUST be protected with the required
safety devices, i.e. a main switch, a slow blow fuse on
each phase and an earth leakage protector in accordance
with the applicable legislation.
NOTICE
See the engineering data book for details.
5.4.3
Specifications for field supplied fuses and
wires
Power supply wiring
Field supplied
fuses
5 Preparation
650
800
1000
1500
2000
198~264 V
198~242 V
2.80
4.39
4.90
8.78
9.80
16
16
16
16
16
0.106×2
0.21×2
0.21×2
0.21×4
0.21×4
1.12×2
1.76×2
1.96×2
1.76×4
1.96×4
16 A
Installer and user reference guide
13