Electrical Wiring - Daikin DBC Series Installation Instructions Manual

15/20/25 ton light commercial packaged heating and cooling units
Hide thumbs Also See for DBC Series:
Table of Contents

Advertisement

DATA
Corner Wei ght - A
Corner Wei ght - B
Corner Wei ght - C
Corner Wei ght - D
Uni t Shippi ng Weight
Uni t Operati ng Wei ght
X (Inches)
Y (Inches)
NOTE: These weights are without accessories installed.
T
O PREVENT SEVERE DAMAGE TO THE BOTTOM OF THE UNIT
FORK LIFT UNIT AFTER WOOD STRUTS HAVE BEEN REMOVED
Bring condenser end of unit into alignment with the curb. With
condenser end of the unit resting on curb member and using curb
as a fulcrum, lower opposite end of the unit until entire unit is
seated on the curb. When a rectangular cantilever curb is used,
care should be taken to center the unit. Check for proper alignment
and orientation of supply and return openings with duct.
R
R
IGGING
EMOVAL
T
O PREVENT DAMAGE TO THE UNIT
AND SPREADER BARS TO REST ON THE ROOF OF THE UNIT
Remove spreader bars, lifting cables and other rigging equipment.

ELECTRICAL WIRING

HIGH VOLTAGE!
D
ISCONNECT ALL POWER BEFORE SERVICING OR
. M
INSTALLING THIS UNIT
ULTIPLE POWER SOURCES MAY
. F
BE PRESENT
AILURE TO DO SO MAY CAUSE PROPERTY
,
DAMAGE
PERSONAL INJURY OR DEATH
HIGH VOLTAGE!
T
O AVOID PERSONAL INJURY OR DEATH DUE TO
,
ELECTRICAL SHOCK
DO NOT TAMPER WITH FACTORY
. T
WIRING
HE INTERNAL POWER AND CONTROL WIRING
OF THESE UNITS ARE FACTORY
BEEN THOROUGHLY TESTED PRIOR TO SHIPMENT
C
ONTACT YOUR LOCAL REPRESENTATIVE IF
.
ASSISTANCE IS REQUIRED
DBC Weights
(lbs)
15 Tons
20 Tons
25 Tons
590
644
626
482
525
464
492
504
501
401
412
518
2080
2202
2377
1965
2085
2109
60"
58"
64.3"
40"
40"
41.3"
CAUTION
CAUTION
,
DO NOT ALLOW CRANE HOOKS
.
WARNING
.
WARNING
-
INSTALLED AND HAVE
.
T
O PREVENT DAMAGE TO THE WIRING
SHARP EDGES
LOCAL CODES AND ORDINANCES
REMOVABLE ACCESS PANELS
C
ONDUIT AND FITTINGS MUST BE WEATHER
WATER ENTRY INTO THE BUILDING
For unit protection, use a fuse or HACR circuit breaker that is in
excess of the circuit ampacity, but less than or equal to the
maximum overcurrent protection device. DO NOT EXCEED THE
MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA
PLATE.
All line voltage connections must be made through weatherproof
fittings. All exterior power supply and ground wiring must be in
approved weatherproof conduit.
,
DO NOT
The main power supply wiring to the unit and low voltage wiring
.
to accessory controls must be done in accordance with these
instructions, the latest edition of the National Electrical Code (ANSI/
NFPA 70), and all local codes and ordinances.
The main power supply shall be three-phase, three wire. The unit
is factory wired for the voltage shown on the unit's data plate.
NOTE: If supply voltage is 208V, all leads on primary of
transformer(s) must be moved from the 230V to the 208V tap.
Main power wiring should be sized for the minimum circuit
ampacity shown on the unit's data plate. Size wires in accordance
with the ampacity tables in Article 310 of the National Electrical
Code. If long wires are required, it may be necessary to increase
the wire size to prevent excessive voltage drop. Wires should be
sized for a maximum of 3% voltage drop.
T
O AVOID PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, USE
ONLY COPPER CONDUCTORS.
L
ABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING
. W
CONTROLS
DANGEROUS OPERATION
.
SERVICING
NOTE: A weather-tight disconnect switch, properly sized for the
unit total load, must be field or factory installed. An external field
supplied disconnect may be mounted on the exterior panel.
Ensure the data plate is not covered by the field-supplied
disconnect switch.
7
CAUTION
,
PROTECT WIRING FROM
. F
OLLOW NATIONAL ELECTRICAL CODE AND ALL
. D
O NOT ROUTE WIRES THROUGH
.
CAUTION
.
CAUTION
CAUTION
IRING ERRORS CAN CAUSE IMPROPER AND
. V
ERIFY PROPER OPERATION AFTER
-
TIGHT TO PREVENT