 Executing Other Commands
 Executing Reader/Writer Setting, Reader/Writer Information Acquisition, or
Reader/Writer Operation Control Commands
EXE
Command code
Command Area
Command parameters
Command data
READY
BUSY
NORM
Response Area
ERR
Response code
Response information
Response data
1. The command code, command parameters, and command data are set from the PLC while the READY
signal is ON.
2. The user (PLC) turns ON the EXE signal. This tells the Reader/Writer to start execution.
3. When the Reader/Writer receives the instruction to start execution, it turns OFF the READY signal and
turns ON the BUSY signal.
4. When communications end normally, the Reader/Writer sets the response code and response data and
turns ON the NORM signal.
5. The user (PLC) detects that the NORM signal has turned ON and reads the response data. After reading
the data, the user (PLC) turns OFF the EXE signal. This tells the Reader/Writer to stop execution.
6. When the Reader/Writer receives the instruction to stop execution, it turns ON the READY signal and turns
OFF the BUSY signal and the ERR signal.
7. When communications end in an error, the Reader/Writer sets the response code and response information
and turns ON the ERR signal.
8. The user (PLC) detects that the ERR signal has turned ON, reads the response code and response
information. After reading the data, the user (PLC) turns OFF the EXE signal. This tells the Reader/Writer
to stop execution.
9. When the Reader/Writer receives the instruction to stop execution, it turns ON the READY signal and turns
OFF the BUSY signal and the ERR signal.
Host Communications Specifications
1
2 3
4 5
6
Section 7
7
8 9
RFID System
179
User's Manual
(PROFINET)