Line Reactor; Drive’s Power Connection Terminals - ABB ACH550 series User Manual

E-clipse bypass configurations (bcr, bdr, vcr, or vdr) for drives (1...400 hp)
Hide thumbs Also See for ACH550 series:
Table of Contents

Advertisement

E-Clipse Bypass Configurations for ACH550 Drives
Fuses, 500...600 Volt, Fuses
HP
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150

Line Reactor

The ACH550 E-Clipse Bypass may contain optional input line reactors to provide
additional input impedance on the VAC line. This impedance is in addition to the
approximately 5% equivalent input impedance provided by internal reactors that are
standard in the drive.
Drive's Power Connection Terminals
The following tables list power and motor cable terminal sizes for connections to an
input circuit breaker or disconnect switch, a motor terminal block and ground lugs.
The tables also list torque that should be applied when tightening the terminals.
Technical Data
500...600 Volt
Identification
ACH550-xxR-02A7-6
ACH550-xxR-03A9-6
ACH550-xxR-06A1-6
ACH550-xxR-09A0-6
ACH550-xxR-011A-6
ACH550-xxR-017A-6
ACH550-xxR-022A-6
ACH550-xxR-027A-6
ACH550-xxR-032A-6
ACH550-xxR-041A-6
ACH550-xxR-052A-6
ACH550-xxR-062A-6
ACH550-xxR-077A-6
ACH550-xxR-099A-6
ACH550-xxR-125A-6
ACH550-xxR-144A-6
Drive Input Fuse Ratings
Frame
Amps
Size
(600V)
R2
30
R2
30
R2
30
R2
30
R2
30
R2
30
R3
60
R3
60
R4
100
R4
100
R4
100
R4
100
R6
200
R6
200
R6
200
R6
200
89
Bussmann
Type
KTK-R-30
KTK-R-30
KTK-R-30
KTK-R-30
KTK-R-30
KTK-R-30
JJS-60
JJS-60
JJS-100
JJS-100
JJS-100
JJS-100
170M1370
or
170M2619

Hide quick links:

Advertisement

Table of Contents