E-Clipse Bypass Configurations for ACH550 Drives
Description section, for a complete list of parameters. E-Clipse Bypass parameter groups 14, 16, 17,
50, 53 and 98 can be changed for more specific network configuration.
Download E-Clipse Bypass Embedded Fieldbus User Manual from http://www.abb.us/drives
STEP 1: Establishing bypass communication with building management system
STEP 2: START/STOP control via serial communication controller
STEP 3: Drive reference and/or PID setpoint via serial communication controller
STEP 4: BACnet Set-up
STEP 5: CYCLE POWER to the system: E-Clipse bypass and drive. (Required)
STEP 6: Network Communication Verification
STEP 1: Establishing Bypass Communication
Bypass
Parameter
9802
Comm Prot Sel
1625
Comm CTL
5301
DV PROT ID
5302
Set desired drive
DV MAC ID
5001
BP PROT ID
5002
BP MAC ID
Note: * If 1625 is set to 0 drive only, bypass control of the motor is from the hand button on the bypass keypad.
STEP 2: START/STOP Control via Serial Communication Controller
Bypass
Paremeter
1601
START/STOP
Note: See E-Clipse Bypass Configuration manual section Parameter Description for complete list of group 16 parameters and settings.
DRIVE
SYSTEM
(PAR 1625 = 0)
DRV & BYPASS
(PAR 1625 = 1)
Select
Select
Communication
Communication
protocol (0 - 5)
protocol (0 - 5)
0*
1
(Factory setting)
READ ONLY
READ ONLY
Set desired drive
network ID
network ID
READ ONLY
READ ONLY
N/A
Set desired
bypass network
ID
DRIVE
SYSTEM
DRV & BYPASS
2
2
Description
0 = NOT SEL
1= STD MODBUS
2 = N2
3 = FLN
4 = EXT FBA
5 = BACNET
0 = DRIVE ONLY (Default)
1= SYSTEM (DRV & BP) Selects comm control mode. In drive
only mode, control of by-pass is not possible. When SYSTEM is
selected both the bypass and drive can be controlled in selected
protocol.
Do not edit. Contains protocol identification and revision.
Default: 1:
Default 128 in BACnetSets the drives unique node address
Must be set different than 5002
Do not edit. Contains protocol identification and revision.
Default: 2
Sets the bypass unique node address
Must be set different than 5302
Description
0 = NOT SEL
1 = DI1
2 = COMM
Selects source for system start command
Embedded Fieldbus and Fieldbus Adapters