Correcting Alarms - ABB ACH550 series User Manual

E-clipse bypass configurations (bcr, bdr, vcr, or vdr) for drives (1...400 hp)
Hide thumbs Also See for ACH550 series:
Table of Contents

Advertisement

E-Clipse Bypass Configurations for ACH550 Drives
Note! For some faults such as motor phase open and motor OC, it is suggested that
you check the drive to motor wiring and/or meggar the motor before attempting to
restart the system on bypass.
History
For reference, the last five fault codes are stored into parameters 0401, 0410, 0419,
0420 and 0421. For the most recent fault (identified by parameter 0401) and Fault 2
(identified by parameter 0410), the drive stores additional data (in parameters
0402...0409 and 0411...00418 respectively) to aid in troubleshooting a problem. For
example, parameter 0405 stores the motor current at the time of the fault.
To clear the fault history (all of the Group 04, Fault History parameters):
1. Using the control panel in Parameters mode, select parameter 0401.
2. Press ENTER.
3. Press Up and Down simultaneously.
4. Press ENTER.

Correcting Alarms

The recommended corrective action for alarms is:
• Determine if the Alarm requires any corrective action (action is not always
required).
• Use the following "Alarm Listing" to find and address the root cause of the
problem.
Diagnostics and Troubleshooting
79