ABB ACH550 series User Manual page 62

E-clipse bypass configurations (bcr, bdr, vcr, or vdr) for drives (1...400 hp)
Hide thumbs Also See for ACH550 series:
Table of Contents

Advertisement

60
Group 16
Code
Name
1626
MODE LOCK
1627
COST/KWH
1628
LEARN
MODE
1629
LEARN TIME
Group 17
Code
Name
1701
OVERRIDE 2
1702
RUN EN OVR
1703
ST EN1 OVR
1704
ST EN2 OVR
1706
ST EN4 OVR
1707
FAULTS OVR
Parameter Descriptions
Resolution
Range
1
0 = NOT SEL
1 = AUTO MODE
2 = LOCAL MODE
0.1 c/kWh
0.0 - 100.00 c/kWh
1
0 = NOT SEL
1 = ENABLED
0.1 Hr
0.0 - 200.0 Hr
Resolution
Range
1
0 = NOT SEL
1 = DI5
2 = COMM
1
0 = ACKNOWLEDGE
1 = DISREGARD
1
0 = ACKNOWLEDGE
1 = DISREGARD
1
0 = ACKNOWLEDGE
1 = DISREGARD
1
0 = ACKNOWLEDGE
1 = DISREGARD
1
0 = ACKNOWLEDGE
1 = DISREGARD
E-Clipse Bypass Configurations for ACH550 Drives
Default
NOT SEL
When Mode Lock is AUTO
(0)
MODE, the control panel will not
allow switching to Hand or Off.
When Mode Lock is LOCAL
MODE, the control panel will not
allow switching to Auto.
7.0 c/kWh
Cost of energy: cents/kWh
NOT SEL
When enabled, bypass learns
(0)
average power consumption
while operating in bypass mode
48.0 Hr
Time that learn mode will be
active after it is enabled
Default
NOT SEL
Selects source for override 2
(0)
command.
DISREGA
Acknowledge or disregard run
RD
enable during override 2.
(1)
DISREGA
Acknowledge or disregard start
RD
enable 1 during override 2.
(1)
DISREGA
Acknowledge or disregard start
RD
enable 2 during override 2.
(1)
DISREGA
Acknowledge or disregard start
RD
enable 4 during override 2.
(1)
DISREGA
Acknowledge or disregard
RD
overrideable bypass faults during
(1)
override 2.
All faults can be overrode except:
3009, 3021, 3022, 3023, 30234,
3027, 3034, 3101, 3202, 3203,
3204, 3205, 3206
Description
Description

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents