Advertisement

E-Clipse Bypass Configurations for ACH550 Drives
Group 16
Code
Name
1619
PAR LOCK
1620
RUN EN TXT
1621
ST EN1 TXT
1622
ST EN2 TXT
1623
ST EN3 TXT
1624
ST EN4 TXT
1625
COMM CTRL
Resolution
Range
1
0 = LOCKED
1 = OPEN
1
0 = RUN ENABLE
1 = DAMPER END SWTCH
2 = VALVE OPENING
3 = PRE-LUBE CYCLE
1
0 = START ENABLE 1
1 = VIBRATION SWITCH
2 = FIRESTAT
3 = FREEZESTAT
4 = OVERPRESSURE
5 = VIBRATION TRIP
6 = SMOKE ALARM
7 = SAFETY OPEN
8 = LOW SUCTION
1
0 = START ENABLE 2
...
1
0 = START ENABLE 3
...
1
0 = START ENABLE 4
...
1
0 = DRIVE ONLY
1 = SYSTEM
Default
Description
OPEN
When switched to "LOCKED"
(1)
prevents parameter changes
from panel. Does not affect to
Field Bus writes, expect
changing the lock value itself:
correct password must always be
set first, even in case of Field
Bus.
RUN
Alternative text choices for alarm
ENABLE
4006.
(0)
START
Alternative text choices for alarm
ENABLE
4021.
1
(0)
START
Alternative text choices for alarm
4022.
ENABLE
2
See parameter 1621 for range.
(0)
START
Alternative text choices for alarm
ENABLE
4023.
3
See parameter 1621 for range.
(0)
START
Alternative text choices for alarm
ENABLE
4024.
4
See parameter 1621 for range.
(0)
DRIVE
Selects comm control mode. In
ONLY
drive only mode, control of drive
is made through drive points, and
(0)
control of bypass over comms is
not possible. In system mode,
control of system (bypass or
drive) is made through bypass
points.
Parameter Descriptions
59