Parameter Listing - ABB ACH550 series User Manual

E-clipse bypass configurations (bcr, bdr, vcr, or vdr) for drives (1...400 hp)
Hide thumbs Also See for ACH550 series:
Table of Contents

Advertisement

50
Parameter Descriptions

Parameter Listing

Parameter data is specific to bypass firmware version .
Group 01
Code
Name
0101
MOTOR
CURR
0102
INPUT VOLT
0103
DI STATUS
0104
RO STATUS
0105
PCB TEMP
0106
KW
HOURS (R)
0107
COMM RO
0108
RUN TIME(R)
0109
ON TIME 1(R)
0110
ON TIME 2(R)
0111
A-B VOLT
0112
B-C VOLT
0113
C-A VOLT
0114
MWH(R)
0115
COST
SAVED(R)
0116
CO2
SAVED(R)
(R) Can be reset by pressing UP and DOWN buttons simultaneously when in parameter set mode.
Parameter Descriptions
Resolution
0.1 A
1 V
1
000000 - 111111
1
00000 - 11111
0.1 ºC
1 kWh
0 - 65535
1
0-FFFFh
1 hr
0 - 65535 hr
1 day
0 - 65535 days
2sec
00:00:00 - 23:59:58
1 V
1 V
1 V
0.001 MWH -
0.001 MWH - 65535 MWH
1 MWH
0.001 K$ - 1
0.001 K$ - 65535 K$
K$
0.1 tn
0.1 - 6553.5 tn
E-Clipse Bypass Configurations for ACH550 Drives
Range
Default
0
0
0
0
0
0
0
Description
Display motor current in any mode.
Average of line-line input voltages
DI1-> 110010 <- DI6
RO1-> 11001 <- RO5
Temperature of bypass board
Bypass-mode kilowatt hours
(resettable).
Serial link control word that can be
linked to relay output control (see
group 14)
Bypass-mode run time (resettable).
Total power on time of bypass,
days (resettable)
Total power on time of bypass,
hr:min:sec (resettable)
Phase A - Phase B voltage
Phase B - Phase C voltage
Phase C - Phase A voltage
Drive kWh savings over bypass
operation (resettable)
Drive cost savings over bypass
operation (reset by parameter
0114)
Drive CO2 savings over bypass
operation (reset by parameter
0114)

Hide quick links:

Advertisement

Table of Contents
loading